PREMTBVC Owners Manual

44
MultiSITE CRC 2 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
Zigbee Configuration
Press the Zigbee* settings button on the
Network Config screen to display the Zig-
bee Configuration screen. Zigbee settings
button is only available when Zigbee is
present onboard or an option card has been
installed in the controller.
*Zigbee is a registered trademark of the Zigbee Alliance.
1/3 Zigbee Config
Security
Channel
Node type
Low
11
Coord.
Network status
Online
PAN ID
Permit join
Off
20
After setting Node type, PAN ID and
Channel values, wait for Network status
to change to Online before attempting
to pair sensors in Zigbee Ecosystem
section
Enable Permit join when ready to begin
pairing sensors and disable immedi-
ately after pairing sensors. This control
is duplicated in the Sensor section for
sensor pairing convenience.
Parameter Parameter Settings Denition
Node type  Set Node type to Coord if controller will be responsible for
controlling Zigbee sensor network.
Pan ID 

Default value = 0

Zigbee coordinators. For every Controller reporting to a
coordinator, make sure to set the SAME channel value both on
the coordinator and the Controllers.
The default value of 0 is NOT a valid PAN ID. The valid range of
available PAN ID is from 1 to 1000.
Channel Channel selection
Using channels 15 and 25 is
recommended.
The valid range of available channels
is from 11 to 25.

Default value = 10


a coordinator, be sure you set the SAME channel value both on
the coordinator and the Controller(s).
The default value of 10 is NOT a valid channel.
Security Zigbee network security level for support of
Green Power / ZigBee 3.0

Default value = Low
If new application and sensors have a “G” in the model number,
sensors are Green Power compliant and Normal setting can be
used. If sensors are already commissioned and it is not known if
they are Green Power compliant, leave at default setting.
Network status Read only 





