PREMTBVC Owners Manual
45
User Interface Guide
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
Zigbee Configuration – continued
Press the right arrow on the Zigbee Configuration screen to display the second page of the Zigbee Configuration
screen. The blue fields indicate the controller is paired with a sensor. Press the right arrow on the second screen to
display the third screen.
COM address
254
Short address
0x0000
2/3 Zigbee Configuration
IEEE address:
0012B00194CF3A
Zigbee revision:
d31.00-8-67840ae
Door contact
status if installed
Zigbee module
FW version
Indicates if the door
contact is installed
IEEE address (MAC
address) of Zigbee
module
Parameter Parameter Settings Denition
COM address
Default value = On
devices from joining the network through this controller.
Short address Default = 0x0000 The unique ZigBee short address is generated once a
wireless device joins a ZigBee network.
Win Interlock
Default = Disable (0)
Interlocks operation of IDU with status of window as
for a delay period longer than set by the Win Delay
control. If Window is closed, IDU will turn back on (A)
intervention is required at remote controller once the
functionality with a door application, simply call the door
a window when the Dr/Win switch is installed through the
Zigbee pairing screen.
Win Delay
1 min (2), 2 min (3), 5 min (4)
Default value = 0 min (0)
Sets the delay period for the Win Interlock feature that
Win Interlock
Disable (0)
Win Delay
1 min (2)
3/3 Zigbee Configuration