PREMTBVC Owners Manual

68
MultiSITE CRC 2 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
BACNET POINTS
BACnet Object Name Object
Type
BACnet
Instance
Read/
Write
# Facets Index Text Default Value Description
TempUnits MV 51 Write 2 1
2
°C (0)
°F (1)
°F (1) Temperature Units Setting (°F
or °C)
Relative humidity sensor MV 149 Write 22 1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
None
Internal
ZB 1
ZB 2
ZB 3
ZB 4
ZB 5
ZB 6
ZB 7
ZB 8
ZB 9
ZB 10
ZB 11
ZB 12
ZB 13
ZB 14
ZB 15
ZB 16
ZB 17
ZB 18
ZB 19
ZB 20
Internal Humidity Sensor Input Selec-
tion
CO2 source MV 150 Write 22 1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
None
Local
ZB 1
ZB 2
ZB 3
ZB 4
ZB 5
ZB 6
ZB 7
ZB 8
ZB 9
ZB 10
ZB 11
ZB 12
ZB 13
ZB 14
ZB 15
ZB 16
ZB 17
ZB 18
ZB 19
ZB 20
None CO2 Sensor Input Selection
ADR Enable MV 152 Write 2 1
2
󰀨
On
󰀨 ADR Enable/Disable