PREMTBVC Owners Manual
70
MultiSITE CRC 2 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
BACnet Object Name Object
Type
BACnet
Instance
Read/
Write
# Facets Index Text Default Value Description
DisplayShowSpaceTemp MV 505 Write 2 1
2
Show
Hide
Show Show or Hide Space Tem-
perature Value
DisplayShowFanSpeed MV 506 Write 2 1
2
Show
Hide
Show Show or Hide Fan Speed
Setting
DisplayShowHumidity MV 507 Write 2 1
2
Show
Hide
Show Show or Hide Humidity Value
DisplayShowAirQuality MV 784 Write 2 1
2
Show
Hide
Show Show or Hide Air Quality (for
unhealthy levels only)
DisplayShowCO2 MV 792 Write 2 1
2
Show
Hide
Show Show or Hide CO2 Value
TempSenseLoc MV 516 Write 3 1
2
3
RC (1)
IDU (2)
2TH (3)
RC (1) Temperature Sensing Loca-
tion Setting
MV 528 Write 2 1
2
On
MV 531 Write 2 1
2
On
MV 532 Write 2 1
2
MV 533 Write 2 1
2
SingleDualSP MV 538 Write 2 1
2
Single SP
Dual SP
Dual SP Single or Dual Setpoint Set-
ting
OverrideMode MV 700 Write 6 1
2
3
4
5
6
Cool
Heat
Fan
Auto
Dry
Auto Mode Override Setting
OverrideFanSpeed MV 701 Write 7 1
2
3
4
5
6
7
Low
Med
High
Auto
Slow
Low-Med
Med-High
Med Fan Speed Override Setting
BACNET POINTS