*Minimum Circuit Ampacity
**Maximum Overcurrent Protection
All equipment single phase.
NOTE: Please see local electrical codes for proper
wire specifications.
Please choose a proper wire size based on local and state code
Refrigerant Line Specifications***
Zone
Type Model BTUs Pipe Size Additional Max. Pipe Max.
Liquid Suction Refrigerant Length Elevation
Art Cool™
Premier
Single Zone
H/P
LS090HYV
9,000 1/4” 3/8” 0.22 oz./ft. 49’ 32’
H/P LS120HYV 12,000 1/4” 3/8” 0.22 oz./ft. 49’ 32’
Art Cool™
Gallery
Single Zone
H/P
LA096HNP
9,900 1/4” 1/2” 0.22 oz./ft. 49’ 23’
H/P LA126HNP 11,500 1/4” 1/2” 0.22 oz./ft. 49’ 23’
Electrical Specifications
Zone
Type Model BTUs Voltage Rated MCA* MOP**
Indoor Outdoor Amps
Art Cool™
Premier
Single Zone
H/P
LS090HYV
9,000 230/208 230/208 8.7 10 15
H/P LS120HYV 12,000 230/208 230/208 8.7 10 15
Art Cool™
Gallery
Single Zone
H/P
LA096HNP
9,900 36V DC 115 10.5 14.3 20
H/P LA126HNP 11,500 36V DC 115 10.5 14.3 20