Brochure

Product
52
Flex Multi
Dual-, Tri-, & Quad Zone
Electrical & Refrigeration
Quick Reference
Zone Type Model Voltage Running Current MCA MOP
Indoor Outdoor
Flex Multi
Indoor Units
H/P LMN096HVT 208/230 - 0.20 - -
H/P LMAN095HVT 208/230 - 0.15 - -
H/P LMDN095HV 208/230 - 0.25 - -
H/P LMN126HVT 208/230 - 0.20 - -
H/P LMAN125HVT 208/230 - 0.15 - -
H/P LMDN125HV 208/230 - 0.25 - -
H/P LMCN125HV 208/230 - 0.25 - -
H/P LMN186HVT 208/230 - 0.30 - -
H/P LMAN185HVT 208/230 - 0.15 - -
H/P LMDN185HV 208/230 - 0.25 - -
H/P LMCN185HV 208/230 - 0.25 - -
Flex Multi Outdoor Units
H/P LMU187HV - 208/230 - 11.0 15
H/P LMU247HV - 208/230 - 15.4 25
H/P LMU369HV - 208/230 - 16.8 25
Type Model Pipe Size Additional Max. Length Max.
Liquid Suction Refrigerant Each Pipe Elevation
Flex Multi
Indoor Units
H/P LMN096HVT 1/4” 3/8” 0.22 oz./ft. 82’ 49’
H/P LMAN095HVT 1/4” 3/8” 0.22 oz./ft. 82’ 49’
H/P LMDN095HV 1/4” 3/8” 0.22 oz./ft. 82’ 49’
H/P LMN126HVT 1/4” 3/8” 0.22 oz./ft. 82’ 49’
H/P LMAN125HVT 1/4” 3/8” 0.22 oz./ft. 82’ 49’
H/P LMDN125HV 1/4” 3/8” 0.22 oz./ft. 82’ 49’
H/P LMCN125HV 1/4” 3/8” 0.22 oz./ft. 82’ 49’
H/P LMN186HVT 1/4” 1/2” 0.22 oz./ft. 82’ 49’
H/P LMAN185HVT 1/4” 1/2” 0.22 oz./ft. 82’ 49’
H/P LMDN185HV 1/4” 1/2” 0.22 oz./ft. 82’ 49’
H/P LMCN185HV 1/4” 1/2” 0.22 oz./ft. 82’ 49’
Electrical Specifications
Refrigerant Line & Formula Specifications
All equipment is single phase.
NOTE: Please see local electrical codes for proper wire specifications.
Please choose a proper wire size based on local and state code