User Guide

14
MultiSITE CRC 1 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
Conguration Parameters Default Value Parameter Settings
Setpoint cool
Default value: 78°F
Range: 52-99 °F
Setpoint heat
Default value: 68°F
Range: 40-90 °F
System mode
Default value: OFF
Choices: Off, Cool, Heat, Fan, Auto, Dry
Fan Speed
Default value: Low
Choices: Slow, Low, Low-Med, Medium, Med-High, High, Power, Auto
Occ./Unocc.
Default value: Unoccupied
Choice: Unoccupied, Occupied
Daily Schedule Screens continued
06:00AM
05:00PM
Monday Sch e dule
H 74 / 70:O
C 71 / 69:U
Off
--:--
--:--
09:00PM
Copy t o
Delete
H 74 / 70:O
To modify an existing
event, tap either the
left side control to
edit the time or tap
the right-hand side of
the control to re-enter
the event screen and
make your desired
changes.
If desired, use the
'Copy to' button to
copy the schedule
to another day of
the week. First
choose the time of
the event you want
to copy and then
choose ‘Copy to’.
Copy to day(s)
Monday
Tuesday
Wednesday
Thursday
Friday
Sunday
Thursday
Saturday
To delete an event,
tap the time of the
event and then tap
the Delete button.
Choose the day(s)
you want to copy the
event to and then
press the left arrow.
Event Overview Display Parameter Meaning
First Letter Mode (O=off, C=cool, H=heat, F=fan, A=auto, D=dry)
Second Number(s) Set Point(s)
Third Letter Occupancy Status (U=unoccupied, O=Occupied)
Example: H: 74 / 70: O = Heating Mode, Upper setpoint of 74, Lower setpoint of 70, Occupied