User Guide

30
MultiSITE CRC 1 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
Using the Up and Down arrows select
between Heating, Cooling or Off
modes. The Test run will end after 18
minutes and then turn system off. Test
mode can be interrupted by changing
fan speed, set point, or turning off the
IDU from the home screen.
Use this function to enable or
disable Group Control for the
system.
Using the Up and Down arrows select
a guard time of 0, 15, 30, 45 or 60
minutes.
Use this function to enable or
disable Indoor Unit Auto Start.
Master(1)
30 M in(2)
Cooling(1)
Test run(1)
Guard T imer(33)
IDU Au t o Start(39)
Enable(1)
IDU M ode- M/S(8)
Gr p Cn trl Funcs(19)
Di sable(0)
3/4 Installer / General
Conguration Parameters Default Value Parameter Settings
Test run(1)
Default value = Off
Choices: Off(0), Cooling(1), Heating(2)
IDU Mode - M/S(8)
Default value = Slave(0)
Choices: Slave(0), Master(1)
Grp Cntrl Funcs(19)
Default value = Disable(0)
Choices: Disable(0), Enable(1)
Guard Timer(33)
Default value = 15 min(1)
Choices in minutes: 0 min(0), 15 min(1), 30 min(2), 45 min(3), 60 min(4)
IDU Auto Start(39)
Default value = Enable(1)
Choices: Enable(0), Disable(1)
Mode 1(1)
Ref. Noise Red. (48)
4/4 Installer / General
Conguration Parameters Default Value Parameter Settings
Refrig Noise Red. (48)
Default value = Disable(0)
Choices:
0 = "Disable(0)" 1 = "Mode1(1)" 2 = "Mode 2(2)