User Guide

32
MultiSITE CRC 1 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
Fan Settings
Press the Fan Settings button on the Installer screen to display the Fan Settings screen. Press the right arrow
button to display the second page of the Fan Settings screen.
Fan Low(0)
1/2 Fan Settings
Fxd Fan Speed(11)
Cool Therm Off(35)
Fan/Vnt inter(38)
11.9-13.8’(4)
Ceiling height(5)
Fixed H(2)
Static pressure(6)
Fan Off(0)
Fan Off(0)
Use SP(0)
2/2 Fan Settings
Sta Pres Step(32)
Enable(1)
Fan Auto Therm Off
IDU Auto Dry
Disable(0)
Delay Fan Off(46)
Speed By Temp(51)
Disable(0)
Enable(1)
Conguration Parameters Default Value Parameter Settings
Fxd Fan Speed(11)
Default value = IDU Cntrl(0)
Choices: IDU Cntrl (0), No Chng (1)
Fan/Vnt inter(38)
Default value = Fan Off(0)
Choices: Fan Off (0), Fan Slow (1)
Cool Therm Off(35)
Default value = Low(0)
Choices: Fan Low (0), Fan Off (1), No Chng (2)
Ceiling height(5)
Default value = 8.8-10.6'(2)
Choices:
1= "< 8.8' (1) - Low
2 = “8.8-10.6' (2) - Stndrd
3 = “10.5 – 11.8' -High (3)”
4 = “11.9-13.8' - Very High (4)
5= > 13.8' - Extremely High (5)
Static pressure(6)
Default value = Fixed H(2)
Choices: 1 = “Var. H (1)”, 2 = “Fixed H (2)”, 3 = “Var. L (3)”, 4 = “Fixed L (4)”
Sta Pres Step(32)
Default value = Use SP(0)
Choices:
0 = “Use SP (0)”
1 = “SPS 1 (1)”
2 = “SPS 2 (2)”
3 = “SPS 3 (3)”
4 = “SPS 4 (4)”
5 = “SPS 5 (5)”
6 = “SPS 6 (6)”
7 = “SPS 7 (7)”
8 = “SPS 8 (8)”
9 = “SPS 9 (9)”
10 =SPS 10 (10)”
11 = “SPS 11 (11)”
Fan Auto Therm Off
Default value = Disable(0)
Choices: 0 = “Disable (0)”, 1 = “Enable (1)”
IDU Auto Dry
Default value = Disable(0)
Choices: 0 = “Disable (0)”, 1 = “Enable (1)”
Delay Fan Off(46)
Default value = Disable(0)
Choices: 0 = “Disable (0)”, 1 = “Enable (1)”
Speed By Temp(51)
Default value = Disable(0)
Choices: 0 = “Disable (0)”, 1 = “Enable (1)”