CONFIGURATION SCREENS
ZigBee Configuration
Press the ZigBee* Config button on the BMS Config screen to display the ZigBee Configuration screen.
*ZigBee is a registered trademark of the ZigBee Alliance.
1/3 Zigbee Configuration
Zigbee PAN ID
COM address
15
11
254
Zigbee short
0x0000
Node type
Zigbee status
No NWK
Coord.
ZigBee Pro short address. The address
is generated once the device joins a
ZigBee network.
Status of controller detecting a ZigBee
network. Will display Online when con-
nected successfully to network.
Conguration Parameters Default Value Parameter Settings
COM address
Terminal Equipment
Controller networking address
Default value = 254
Range is: 0 to 254
For wireless models, the use of the COM address is not mandatory. COM address is
an optional way to identify a device on the network and is recommended if used with an
MPM.
It is Mandatory for BACnet.
Node type
Coord; Router
Set Node type to Coord if controller will be responsible for controlling Zigbee sensor
network.
ZigBee Pan ID
Personal Area Network Identication
Default value = 0
Range is: 1 to 1000
This parameter (PAN ID) links specic Controllers to specic ZigBee coordinators. For
every Controller reporting to a coordinator, make sure to set the SAME channel value
both on the coordinator and the Controllers.
The default value of 0 is NOT a valid PAN ID. The valid range of available PAN ID is from
1 to 1000.
ZigBee channel
Channel selection
Default value = 10
Range is: 10 to 25
This parameter (Channel) is used to link specic Controllers to specic ZigBee
coordinators. For every Controller reporting to a coordinator, be sure you set the SAME
channel value both on the coordinator and the Controller(s).
Using channels 15 and 25 is recommended.
The default value of 10 is NOT a valid channel. The valid range of available channels is
from 11 to 25.
ZigBee status
(read only)
ZigBee status
The following read only messages show in this eld:
(Not Det): ZigBee Pro module not detected
(Pwr On): ZigBee Pro module detected but not congured
(No NWK): ZigBee Pro congured but no network joined
(Joined): ZigBee Pro network joined
(Online): Communicating