Install Instructions

Mounting the control panel
1. Determine mounting location for panel. If
distance exceeds the length of either the float
switch cables or the pump power cables, splicing
will be required. For outdoor or wet installation,
we recommend the use of a SJE-Rhombus
®
liquid-tight junction box with liquid-tight
connectors to make required connections. You
must use conduit sealant to prevent
moisture or gases from entering the panel.
2. Mount control panel with mounting flanges
furnished with control panel.
3. Determine conduit entrance locations on control
panel. Check local codes and schematic for the
number of power circuits required.
NOTE: Be sure the incoming power, voltage,
amperage, and phase meet the requirements of
the pump motors being installed. If in doubt, see
the pump identification plate for electrical
requirements.
4. Drill proper size holes for type of connectors
being used.
NOTE: If using conduit, be sure that it is of
adequate size to pull the pump and switch cables
through. You must use conduit sealant to
prevent moisture or gases from entering the
panel.
5. Attach cable connectors and/or conduit
connectors to control panel.
FOR INSTALLATION REQUIRING A SPLICE,
FOLLOW STEPS 6-10;
FOR INSTALLATION WITHOUT A SPLICE,
GO TO STEP 11.
6. Determine location for mounting junction box
according to local code requirements. Do not
mount the junction box inside the sump or basin.
7. Mount junction box to proper support.
Installation Instructions
8. Run conduit to junction box. Drill proper size holes
for the type of conduit used. Attach liquid-tight
connectors to junction box.
9. Identify and label each wire before pulling through
conduit into control panel and junction box. Pull
pump power cables and control switch cables
through connectors into junction box. Make wire
splice connections at junction box.
10. Firmly tighten and seal all fittings on junction box.
Insure all cable connectors are liquid-tight and
sealed.
11. If a junction box is not required, connect pump
and float wires to proper position on terminals.
See schematic inside control panel for terminal
layouts.
12. Connect control/alarm and pump power
conductors to proper position on terminals. See
schematic inside control panel for terminal
connections.
NOTE: It is the recommendation of the factory to use
separate pump and control/alarm power sources.
VERIFY CORRECT OPERATION OF
CONTROL PANEL AFTER INSTALLATION
IS COMPLETE.
7249000A
- 3 -