13.01 FACTORY ASSEMBLED TANK SYSTEMS WITH GUIDE RAIL AND QUICK DISCONNECT DISCHARGE
______ Guide factory mounted rail system with pump suspended by means of bolt on quick disconnect which is sealed by means of nitrile
grommets or o-rings. The Discharge piping shall be schedule 80 PVC and furnished with a check valve and PVC shut-off ball valve. The
Tank shall be wound fiberglass or roto-molded plastic. An inlet hub shall be provided with the fiberglass systems.
______ Stainless steel Guide Rail
______ Zinc plated steel Guide Rail
______ "diameter of basin size
______ "height of basin size
______ "distance from top of tank to discharge pipe outlet
______ Fiberglass cover
______ Structural foam polymer cover
______ Steel cover
______ Simplex System with Outdoor panel and alarm
______ Duplex System with Outdoor panel and alarm
______ Simplex System with Indoor panel and alarm
______ Duplex System with Indoor panel and alarm
______ Separate Outdoor Alarm
______ Remote Outdoor Alarm
14.01 TESTING
The pump shall have a ground continuity check and the motor chamber shall be Hi-potted to test for electrical integrity, moisture content
and insulation defects. The motor and volute housing shall be pressurized, and an air leak decay test is performed to ensure integrity of the
motor housing. The pump shall be run, voltage current monitored, and the tester checks for noise or other malfunction.
15.01 QUALITY CONTROL
The pump shall be manufactured in an ISO 9001 certified Facility.
16.01 WARRANTY
Standard limited warranty shall be 3 years.