Maintenance
1. The preset level control must be kept clean and free of rust, mud, soap or any conductive material.
2. Every year clean probes keeping them free of debris, calcium or iron deposits.
3. Fuses in control panel are 5mm X 20mm 1/2amp for F1 and 5mm X 20mm 1amp for F2.
(Spare fuses are included for your convenience)
4. Every year replace 9 Volt Battery in Remote Alarm.
Trouble Shooting
Symptom Possible Cause Action
Pump does not run Panel Power Cord Unplugged Plug in Outlet, Check Power
Pump not plugged into panel Plug pump to panel plug
Defective Contactor Replace Contactor
Loose level sensor wires Tighten connections
Pump failure Replace pump
Pump turns off before Poor pump ground or system ground Check grounding system
bottom probe