Owners manual
Table Of Contents
- Important Safety Precautions
- Save These Instructions
- Glossary of Symbols
- 1.0 Product Description
- 1.1 Features
- 1.2 Available Models
- 1.3 Appearance and Components
- 1.3.1 Front Panel and Controls
- 1.3.2 Rear Panel Features
- Figure 2 Rear panel components—Liebert GXT4 120V rack/tower, 500, 700, 1000VA model
- Figure 3 Rear panel components—Liebert GXT4 120V rack/tower, 1500VA model
- Figure 4 Rear panel components—Liebert GXT4 120V rack/tower, 2000VA model
- Figure 5 Rear panel components—Liebert GXT4 120V rack/tower, 3000VA model
- Figure 6 Rear panel components—Liebert GXT4 208V rack/tower, 3000VA model
- 1.4 Major Components
- 1.5 Operating Mode
- 2.0 Installation
- 3.0 Operation and Display Panel
- Figure 14 Operation and display panel
- 3.1 LED Indicators
- 3.2 Control Buttons
- 3.3 LCD
- 3.4 Menu Structure
- Figure 15 Menu structure
- 3.4.1 Startup Screen
- 3.4.2 Default Screen
- 3.4.3 Main Menu Screen
- 3.4.4 Prompt List
- 3.4.5 Warning List
- 3.4.6 Fault List
- 4.0 Operation
- 5.0 Communication
- 6.0 Maintenance
- 7.0 Troubleshooting
- 8.0 Battery Cabinet
- 9.0 Specifications
- Table 13 Specifications of GXT4-500RT120 - GXT4-700RT120 and GXT4-1000RT120 models
- Table 14 Specifications of GXT4-1500RT120 - GXT4-3000RT120 and GXT4-3000RT208 models
- Table 15 Battery cabinet specifications
- Table 16 Operating temperature parameters
- Table 17 Battery run times
- 9.1 Product Warranty Registration
- 9.2 Technical Support

Operation and Display Panel
31 Liebert
®
GXT4
™
3.4.6 Fault List
All UPS fault messages are described in Table 7.
If a fault occurs, the UPS automatically switches to Bypass Mode. The original operating mode will be
maintained only in the case of a battery disconnection fault. The fault message alternates with UPS
Mode once a second, the red fault indicator on the operation and display panel lights up and the alarm
sounds continuously.
If a fault occurs:
1. Enter the ALARM CONTROL screen (see Figure 36), and select AUDIBLE ALARM ON or
AUDIBLE ALARM OFF to switch the alarm On or Off.
2. Enter the EVENT LOG screen (see Figure 38), and select VIEW LOG to view the entire Event
log.
Table 7 Fault list
Fault Description
UPS Self-Test Failed The battery is bad or weak or not connected.
UPS Overload The UPS is overloaded.
Inverter Out Of Order The inverter has failed.
Battery Weak/Bad The battery is bad or weak.
Output Short Circuit The output connection is short-circuited.
DC Bus Overvoltage The DC bus is faulty.
UPS Overtemperature Overtemperature occurs to the UPS and the UPS will transfer to Bypass mode.
Charger Out Of Order The charger has failed.
Fan Out Of Order At least one fan is failed.
DC Bus Discharge Fail DC-DC failure occurs.
Rectifier Out Of Order Rectifier failure occurs.
NOTE
There will be a short delay before the EVENT LOG screen displays the historical fault log to
allow the log to load.










