Liebert® GXT4™ 208V, 5000-10,000VA, 6000RTL630 User Manual
TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.0 PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.0 OPERATION AND DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 3.1 LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 3.2 Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 3.3 LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 8.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 8.1 Auto-Learning Battery Run Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 8.2 Product Warranty Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 43 Disconnecting the battery plug and battery receptacle (front view) . . . . . . . . . . . . . . . . . . . . . . . 44 Figure 44 Pulling out the battery packs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Figure 45 Removing power module from Liebert GXT4 8000 and 10,000VA models . . . . . . . . . . . . . . . . . .
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions. Read all safety and operating instructions before operating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This equipment can be operated by individuals without previous training. This product is designed for commercial/industrial use only.
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT4 complies with the limits for a Class A digital device, pursuant to Part 15 of FCC rules. Operation is subject to the following conditions: • This device may not cause harmful interference. • This device must accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.
GLOSSARY OF SYMBOLS Risk of electrical shock ! Indicates caution followed by important instructions AC input AC output i - Requests the user to consult the manual + Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 R Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage WEEE 3 Liebert® GXT4™
Product Description 1.0 PRODUCT DESCRIPTION The Liebert GXT4 is a compact, online uninterruptible power system (UPS) that continuously conditions and regulates its output voltage. The UPS is designed to supply microcomputers and other sensitive electronic equipment with clean sine wave input power, 5000VA, 6000VA, 8000VA and 10,000VA. Upon generation, AC power is clean and stable.
Product Description Figure 1 Liebert GXT4 5000VA and 6000VA, front view Upper Bezel Operation and Display Panel Upper Bezel Operation and Display Panel Lower Bezel and Battery Access Door 1.3.
Product Description Figure 3 Liebert GXT4-6000RTL630, rear view REPO Connection Block USB Port Terminal Block Communication Output Breaker for L6-20R #2 and #3 Output Breaker for L6-30R #4 External Battery Connector Liebert IntelliSlot Port Input Breaker for L6-30P #1 IT Power System Access Cover Maintenance Bypass Breaker 2 1 Figure 4 Output Breaker for L6-30R #5 5 4 3 Liebert GXT4 8000VA and 10,000VA rear view Maintenance Bypass Switch Liebert IntelliSlot Port Terminal Block Communication
Product Description 1.4 Removable Power Distribution Box The UPS is shipped with a power distribution pack installed. This box contains the UPS input circuit breaker.
Product Description Figure 6 Power distribution models for 8000VA and 10,000VA models of Liebert GXT4 p ; similar features on other distribution boxes arranged differently 5-20R Output Receptacles Output Circuit Breaker Switch for L6-30R Pigtail #1 L6-30ROutput Receptacles Push Button Circuit Breakers for 5-20R Receptacles 2 5-20R Output Receptacles PD2-101 Receptacles: two L6-30R; eight 5-20R 1 Output Circuit Breaker Switch for L6-30R Pigtail #2 PD2-105 Receptacles: four 5-20R two L5-30R two L5-20
Product Description Figure 7 Power distribution models for 8000VA and 10,000VA models of Liebert GXT4 (continued) PD2-107 Receptacles: four L5-20R; four 5-15R PD2-108 Receptacles: two L6-30R; two L6-20R PD2-201 Receptacles: two IEC320-C19 eight IEC320-C13 PD2-202 Receptacles: (12) IEC320-C13 PD2-109 Receptacles: two L14-30R PD2-204 Receptacles: two IEC309-32A four IEC320-C13 PD2-200 Receptacles: four IEC320-C19 four IEC320-C13 9 Liebert® GXT4™
Product Description 1.5 Internal Battery Packs The UPS has two internal battery packs behind a battery access door on the front of the unit. Each internal battery pack is fitted with a connector to link to the UPS. Figure 8 Internal battery pack with connector Battery Handle GXT4 10,000 Battery Pack shown; 5000 and 6000VA battery packs have same features Battery Connector Front of Battery Pack 1.
Product Description 1.6.3 Inverter In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter receives its required energy from the battery through the DC-to-DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power. 1.6.
Product Description 1.7.2 Manual Bypass Mode Manual Bypass Mode occurs when the unit is manually placed in internal bypass by navigating the LCD menu to select 3 Control > 1 Turn On & Off > Turn UPS Bypass. Bypass operation is indicated by an audible alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 - Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to the connected load.
Product Description 1.7.6 Active ECO Mode All Liebert GXT4 models can operate in Active ECO Mode. In this mode, the connected equipment is powered through the bypass path to increase efficiency, reducing the electrical costs. Active ECO mode keeps the rectifier and inverter operating, allowing the inverter to remain synchronized to bypass. This synchronization allows the transfer of the connected equipment to UPS inverter power almost seamlessly if bypass power falls outside the user-set limits.
Installation 2.0 INSTALLATION Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 4.2 - Starting the UPS. 2.1 Unpacking and Inspection Unpack the UPS and conduct the following checks: • Inspect the UPS for shipping damage. Report any shipping damage to the carrier and your local dealer or Emerson® representative immediately. • Check the accessories against the delivery list.
Installation 2.4 Install the Main Cabinet The Liebert GXT4 may be installed in either a tower configuration or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions in either 2.4.1 - Tower UPS Installation or 2.4.2 - Rack Installation. 2.4.1 Tower UPS Installation To install the Liebert GXT4 as a tower: 1. Take the support bases out of the accessories bag (see Figure 9).
Installation d. Replace the front plastic bezel cover on the Liebert GXT4. At this point, the UPS operation and display panel and logo have been rotated 90 degrees clockwise, which provides upright viewing for users. 5. Place the Liebert GXT4 and any battery cabinets on the support bases. Each Liebert GXT4 needs two support assemblies. 2.4.2 Rack Installation The Liebert GXT4 UPS and external battery cabinets (EBC), when installed in a rack enclosure, must be supported by a shelf or rack-mount rails.
Installation 8. Use the included configuration program or the LCD to program the UPS with the number of external battery cabinets connected. Instructions for the configuration program are in 5.2.1 Configuration Program. 9. The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 21. NOTE When removing the External Battery Cabinet, the circuit breaker on the rear of the cabinet must be turned off before disconnecting the cable.
Installation 2.6.1 Remove the Power Distribution Box from 5000 and 6000VA Models 1. Manually transfer the connected equipment to the internal bypass. a. From the main menu select CONTROL, then press Enter. b. Select TURN ON & OFF and press Enter. c. Select TURN UPS BYPASS and press Enter. The UPS will transfer the connected loads to the internal bypass. (For help, refer to 4.4 - Manual Bypass.) d. Loosen the captive screw over the maintenance bypass breaker (see Figure 13 for the breaker’s location). e.
Installation Figure 14 Power distribution box removal from 8000 and 10,000VA models Extract screws at these places Pigtails removed for clarity Tabs slip into slots on UPS 2.6.3 Install the Power Distribution Box on 5000 and 6000VA Models 1. Align the connectors and press the power distribution box onto the UPS. 2. Hold the box firmly against the UPS and tighten the captive screws except the one over the maintenance bypass breaker. 3. Turn the output and input breakers On. 4.
Installation 2.6.5 Distribution Box Electrical Connections Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.
Installation Figure 16 Terminal block connections Liebert GXT4-5000 and 6000RT208 L2 N L1 L2 OUTPUT N L1 INPUT Liebert GXT4-8000 and 10,000RT208 L2 N L1 L2 OUTPUT N L1 INPUT NOTE 1. Emerson recommends installing a UL489-approved breaker upstream of unit. 2. The installer must provide circuit breaker protection according to local codes. The utility disconnect should be within sight of the UPS or have appropriate an appropriate lock-out.
Operation and Display Panel 3.0 OPERATION AND DISPLAY PANEL This chapter describes the Liebert GXT4 controls, particularly the operation and display panel on the front of the Liebert GXT4. The panel has four control buttons, seven LED indicators and a liquid crystal display (LCD), as shown in Figure 17. Figure 17 Operation and display panel Battery Indicator Inverter Indicator Fault Indicator Bypass Indicator LCD Panel ECO Mode Indicator ESC Button Enter Button UP Button 3.
Operation and Display Panel 3.2 Control Buttons The four control buttons on the front of the operation and display panel are: • • • • ESC Up Down Enter Figure 17 shows the buttons’ locations; their descriptions and functions are shown in Table 5. Table 5 3.3 Control buttons Control Buttons Description ESC Button Pressing this button returns to the previous menu or aborts any change in the input data field before confirming.
Operation and Display Panel 3.4 Menu Structure The menu structure of the LCD is shown in Figure 18. Figure 18 Menu structure Audible Alarm Output Startup on Bypass Load Status UPS Battery Enable Auto Restart Time Since Startup Frequency Selection Start Windows System Status Enable Auto Shutdown Input Output Level Selection Configuration Battery Cabinets Turn UPS On/Off Turn UPS On Turn UPS Off BATT Low Battery Time Warning Batt Test Interval Main Menu Control Alarm Control 1.
Operation and Display Panel 3.4.1 Startup Screen When the Liebert GXT4 is starting up, it initiates a self-test and displays the screen shown in Figure 19 for about 10 seconds. Figure 19 Startup screen EMERSON Network Power After about 10 seconds, the LCD shows one of the On screens in Figure 20; the screen shown depends on whether input power is available. Figure 20 Startup screens TURN ON UPS YES NO O/P: 0V HZ 0.0A I/P : 230 V 50HZ 0.
Operation and Display Panel 3.4.2 Default Screen Press any button in the START SUCCESSFUL screen to enter the default interface, shown in Figure 22. Figure 22 Default screen GXT4-UPS 3KVA Values shown will vary according to installation and configuration. O/P: 230V 50HZ 11.7A I /P: 230V 50HZ 13.1A BATT: 100 % 3MINS LOAD: 100% In the default screen, the LCD shows the UPS model, output parameters, input parameters, battery capacity with run time estimate and load percentage.
Operation and Display Panel Figure 24 Status screens OUTPUT LOAD VOLTAGE : 120V FREQUENCY : 60HZ CURRENT : 17.6A POWER : 2112 KWH CAP : WATT : VA : INPUT VOLT FREQ CURR POWER 90% 1620W 1800VA : : : : 120V 60 HZ 18.6A 97KWH BATTERY TIME SINCE STARTUP CAPACITY : RUNTIME : VOLTAGE : 90% 100 MINS 80V 05D 15H 30M CONFIGURATION Screen Select MAIN MENU > CONFIGURATION to enter the Configuration menu. This menu has seven submenus, as shown in Figure 25. Figure 25 CONFIGURATION screen 1. 2. 3. 4. 5.
Operation and Display Panel UPS Screen Select MAIN MENU > CONFIGURATION > UPS to enter the UPS screen. This menu has six screens, as shown in Figure 26. Figure 26 UPS screens AUDIBLE ALARM STARTUP ON BYPASS GUARANTEE SHUTDOWN OFF NO NO ENABLE AUTO RESTART FREQUENCY SELECTION VOLTAGE SELECTION YES AUTO - BYPASS ENABLE 230 Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings.
Operation and Display Panel Press the Up or Down button to increase or decrease the value of the settings, and press the Enter button to confirm it. ECO Mode Screens Select MAIN MENU > CONFIGURATION > ECO MODE to enter the ECO MODE screens, as shown in Figure 28. Figure 28 ECO Mode screen ECO MODE VOLTAGE TOLERANCE ON 10% FREQUENCY TOLERANCE REQUALIFICATION TIME 3 Hz 5 MINS Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings.
Operation and Display Panel Select 1 LANGUAGE and press the Enter button to enter the LANGUAGE screen, as shown in Figure 30. The Liebert GXT4 is capable of supporting multiple languages. For the list of supported languages and instructions on how to upload them, refer to the Configuration Program user manual on the included CD. Figure 30 Language screen 1 English 2 Select ‘2 COLOR’ and press the Enter button to enter the COLOR screen, as shown in Figure 31.
Operation and Display Panel Control Screen Select Main Menu -> 3 CONTROL to enter the CONTROL screen. This screen has three submenus, as shown in Figure 33. Figure 33 Control screen 1 TURN ON & OFF 2 ALARM CONTROL 3 BATT TEST In the CONTROL screen, press the Up or Down button to move the cursor to the required item, and press the Enter button to enter its submenu. TURN ON & OFF screen Select Main Menu -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen.
Operation and Display Panel BATT TEST screen Select MAIN MENU -> 3 CONTROL -> 3 BATT TEST to enter the BATT TEST screen, as shown in Figure 36. Figure 36 Batt Test screen 1 START 2 CANCEL 3 BATT TEST RESULT Log Screen Select MAIN MENU -> 4 LOG to enter the LOG screen. This screen has two submenus, as shown in Figure 37.
Operation and Display Panel ABOUT Screen Select Main Menu> ABOUT to enter the ABOUT screen, as shown in Figure 39. Figure 39 About screen PN: GXT4-2000 RT230 SN:1XXX60XXX1AFCXX FW VER: U100D100 HW VER: H100 The ABOUT screen displays UPS model, serial number, software version and hardware version. Network Select MAIN MENU>NETWORK to enter the NETWORK screen. The NETWORK screen displays the MAC address and the IPv4 IP address.
Operation and Display Panel 3.4.4 Prompt List A prompt screen is displayed during the operation of the system to alert you to certain conditions and/or to require your confirmation of a command or other operation. See Table 6 for the system prompts and meanings. Table 6 3.4.5 Prompts and meanings Prompt Meanings Mains Power Restored The mains power returns and the UPS transfers back to mains (AC) mode.
Operation and Display Panel 3.4.6 Fault List All UPS fault messages are described in Table 8. Table 8 Fault list Fault Description UPS Self-Test Failed The battery is bad or weak or not connected. UPS Overload The UPS is overloaded. Inverter Out Of Order The inverter has failed. Battery Weak/Bad The battery is bad or weak. Output Short Circuit The output connection is short-circuited. DC Bus Overvoltage The DC bus is faulty.
Operation 4.0 OPERATION This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting mains power from the UPS. NOTE The Liebert GXT4’s battery has been fully charged before delivery, but some charge will be lost during storage and shipping. To ensure that the battery has adequate reserve power to protect the connected load, charge the battery for three hours before putting the UPS into service. 4.
Operation 4.5 Shut Down the Liebert GXT4 To shut down the UPS from the LCD: 1. From the Main Menu select CONTROL, press Enter, then select TURN ON & OFF. 2. Press the enter key. 3. Select TURN UPS OFF, then press Enter. Press either the up or down button to move the cursor to confirm the turn off command and press enter. Note: the UPS will sound an audible alarm, this is normal. 4. Power to the connected equipment is now off.
Communication 5.0 COMMUNICATION This section describes the three types of communication ports on the rear of the UPS: • Liebert IntelliSlot® port • USB port (standard B-type) • Terminal Block Communication ! CAUTION To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables. 5.
Communication 5.2 USB Port Communication The standard B-type USB port is used to connect the UPS and network server or other computer system using Liebert MultiLink®. A standard B-type USB port is provided to allow connection to a computer or network server. The USB port can be used to communicate with the Liebert GXT4 configuration program (see section 5.2.1 for details) or Liebert MultiLink (refer to 5.1.1 - Liebert MultiLink for description) that is provided on the CD that is included with the UPS. 5.
Communication 5.3 Terminal Block Communication The Terminal Block includes eight pins, as shown in Figure 41. Figure 41 Terminal Block Communication pin layout 5.3.1 1 2 Any Mode Shutdown 3 4 Battery Mode Shutdown 5 6 On Battery Mode 7 8 Low Battery Any Mode Shutdown The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads.
Communication 5.3.2 Battery Mode Shutdown Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active. Battery Mode Shutdown can be performed locally or remotely: • Local Battery Mode shutdown can be performed by shorting Pin3 and Pin4.
Communication 5.4 Remote Emergency Power Off The UPS is equipped with a Remote Emergency Power Off (REPO) connector. The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.
Maintenance 6.0 MAINTENANCE This section describes replacing the internal battery pack, precautions, checking the Liebert GXT4’s status and checking UPS functions. 6.1 Replacing the Internal Battery Pack The Liebert GXT4 is designed to allow the user to replace the internal battery pack safely. Refer to Table 10 for internal battery pack part numbers for Liebert GXT4 UPS.
Maintenance 6.1.1 Battery Replacement Procedures 1. Gently remove the front plastic bezel cover from the UPS. 2. Loosen and remove the six screws on the battery door, as shown in Figure 42. 3. Lay the battery door and screws aside for reassembly. Figure 42 Removing the front plastic bezel cover and battery door Battery Door Screws, 6 8000VA / 10,000VA model shown; 5000VA & 6000VA model arrangement is the same except smaller Front Bezel 4.
Maintenance Figure 44 Pulling out the battery packs 5000 & 6000 VA models 6000RTL630, 8000VA / 10,000VA model Internal Battery Pack Internal Battery Pack (one of 2) Battery Handle Battery Handle Pull Out with Battery Handle Each model has two battery packs. Pull Out with Battery Handle 6. Unpack a new internal battery pack. Take care not to destroy the packing. Compare the new and old internal battery packs to make sure they are the same type and model.
Maintenance 6.4 Checking UPS Status Emerson recommends checking the UPS operation status every six months. • Check whether the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an alarm? • Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or Emerson Channel Support. • Check whether the battery is discharging.
Maintenance Figure 45 Removing power module from Liebert GXT4 8000 and 10,000VA models Power module pulled part of the way out of an 8000 or 10,000VA unit 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. Insert the replacement UPS power module. Slide the power module restraint lever back into the locked position. Reconnect the slotted internal battery connectors. Reconnect the external battery cables, if used. Reattach both front cover grilles. Reattach the front plastic bezels.
Troubleshooting 7.0 TROUBLESHOOTING This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation. 7.1 UPS Symptoms The following symptoms indicate the Liebert GXT4 is malfunctioning: • The relative indicators illuminate, indicating the UPS has detected a problem.
Troubleshooting 7.1.2 Audible Alarm An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating status. The audible alarm will sound as described in Table 12.
Specifications 8.0 SPECIFICATIONS Table 14 UPS specifications—5000, 6000, 8000 and 10,000 models Model Number GXT4-5000RT208 GXT4-6000RT208 GXT4-8000RT208 GXT4-10000RT208 Model Rating 4000W/5000VA 4800W/6000VA 7200W/8000VA 9000W/10000VA Dimensions, Rack Mount, W x D x H Unit, in. (mm) 16.9 x 26.1 x 6.8 (430 x 662 x 173) 16.9 x 26.5 x 10.3 (430 x 672 x 261) Shipping, in. (mm) 20.3 x 29.3 x 20.9 (516 x 745 x 530) 20.9 x 29.3 x 22.2 (530 x 745 x 563) Weight lb (kg) Unit, lb (kg) 131.8 (69.
Specifications Table 15 UPS specifications—Liebert GXT4-6000RTL630 Model Number GXT4-6000RTL630 Model Rating 4200W/6000VA Dimensions, Rack Mount, W X D X H, in. (mm) Unit 16.9 x 22.6 x 8.5 (430 x 574 x 217) Shipping 20.3 x 29.3 x 20.9 (516 x 745 x 530) Weight, lb (kg) Unit 132.2 (60) Shipping 156.
Specifications Table 16 Internal battery cabinet specifications GXT4-144VBATKIT GXT4-240VBATKIT GXT4-288VBATKIT GXT4-5000RT208 GXT4-6000RT208 GXT4-6000RTL630 GXT4-8000RT208 GXT4-10000RT208 8.1 x 19.3 x 2.8 (206 x 490 x 70) 7.2 x 15.4 x 4.4 (184 x 390 x 113) 8.1 x 19.7 x 5.3 (207 x 500 x 135) 10.3 x 23.7 x 12.2 (262 x 602 x 310) 10.3 x 18.4 x 7 (262 x 467 x 178) 9.5 x 23.9 x 12.2 (242 x 607 x 310) Unit 75.8 (34.4) 45.4 (20.6) 71.1 (32.3) Shipping 81.1 (36.8) 50.7 (23) 76.4 (34.
Specifications Table 17 External battery cabinet specifications GXT4-144VBATT GXT4-240VBATT GXT4-288VBATT GXT4-5000 & GXT4-6000RT208 GXT4-6000RTL630 GXT4-8000 & GXT4-10000RT208 Unit (with bezel) 16.9 x 26.1 x 3.3 (430 x 662 x 85) 16.9 x 22.6 x 6.8 (430 x 574 x 173) 16.9 x 26.5 x 6.8 (430 x 672 x 173) Shipping 25.8 x 34.3 x 12.3 (655 x 872 x 312) 20.9 x 29.3 x 18.7 (530 x 745 x 475 24.5 x 33.1 x 18.7 (622 x 842 x 475) 99.9 (45.3) 143.3 (65) 167.6 (76.2) 121 (55) 176.
Specifications Table 19 Power distribution box specifications for GXT4-8000RT208 and GXT4-10000RT208 Power Distribution Box Model # POD Model # PD2-101 PD2-102 PD2-103 PD2-104 PD2-105 PD2-106 Dimensions, W x D x H, in. (mm) Unit 7.4 x 5.7 (188 x 145) Shipping 11.9 x 20.6 x 8.7 (302 x 522 x 220) Weight, lb (kg) Unit 4.4 (2) 6.6 (3) 6.6 (3) 6.6 (3) 4.4 (2) 6.6 (3) Shipping 6.6 (3) 8.8 (4) 8.8 (4) 8.8 (4) 6.6 (3) 8.
Specifications Table 21 Battery run time, minutes Number of External Battery Cabinets Internal Battery Internal Battery + 1 External Battery Cabinet Internal Battery + 2 External Battery Cabinets Internal Battery + 3 External Battery Cabinets 208/120 VAC RT Models 208 VAC RT Model Load Percent of Capacity 5 kVA 6 kVA 8 kVA 10 kVA 6 kVA (L630) 10% 129 106 144 112 100 20% 52 46 69 48 50 30% 36 27 43 30 38 40% 25 19 28 21 26 50% 18 14 22 16 19 60% 14 11 18 12
Specifications Table 21 Battery run time, minutes Number of External Battery Cabinets Internal Battery + 4 External Battery Cabinets Internal Battery + 5 External Battery Cabinets Internal Battery + 6 External Battery Cabinets 208/120 VAC RT Models 208 VAC RT Model Load Percent of Capacity 5 kVA 6 kVA 8 kVA 10 kVA 6 kVA (L630) 10% 454 442 463 447 456 20% 323 300 340 310 420 30% 194 161 218 165 304 40% 153 138 164 144 200 50% 134 110 147 122 160 60% 110 92 130
Specifications 8.1 Auto-Learning Battery Run Times As batteries age, the estimated run times may become less accurate. The Liebert GXT4 is programmed to “learn” from a full battery discharge and modify the estimated run time for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures. The UPS will update the anticipated run time calculation only under certain conditions.
Technical Support / Service Web Site www.liebert.com Monitoring liebert.monitoring@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets liebert.upstech@emerson.