Owners manual

Installation
Emerson
®
MPH2
12
2.2 Tool-less Mounting
For tool-less mounting, attach the mounts to the rear of the MPH2 rack PDU, then hang it in the rack
as shown in Figure 10. Torque the screw attaching the mounting button 17 lb-in (2Nm).
Figure 10 Tool-less mounting
Table 1 Hard-wired models—Connection terminal ratings
MPH2 Rating
32A >32A
Conductor Cross-Section Solid, Minimum 0.2mm
²
0.5mm
²
Conductor Cross-Section Solid, Maximum 6mm
²
16mm
²
Conductor Cross-Section Stranded, Minimum 0.2mm
²
0.5mm
²
Conductor Cross-Section Stranded, Maximum 4mm² 10mm
²
Conductor Cross-Section, AWG/kcmil, Minimum 24 20
Conductor Cross-Section, AWG/kcmil, Maximum 10 6
Conductor Cross-Section Stranded, With Ferrule
Without Plastic Sleeve, Minimum
0.25mm
²
0.5mm
²
Conductor Cross-Section Stranded, With Ferrule
Without Plastic Sleeve, Maximum
4mm
²
10mm
²
Conductor Cross-Section Stranded, With Ferrule
With Plastic Sleeve, Minimum
0.25mm
²
²0.5mm
²
Conductor Cross-Section Stranded, With Ferrule
With Plastic Sleeve, Maximum
4mm
²
10mm
²
Table 2 Terminal tightening torque
Tightening Torque
MPH2 Rating
32A >32A
Minimum 0.6 Nm 1.5Nm
Maximum 0.8Nm 1.8Nm
NOTE
Brackets are not supplied. A range of brackets for Emerson and other manufacturers’ racks are
available as accessories.
Insert the Button Mount
into the Keyhole Slot
Torque screw
17 lb-in (2Nm)
Button Mount