5.0 TROUBLESHOOTING
LED Indication
(One or All LED’s)
Audible
Alarm
Condition Status/Recommended Action
Color
State/Flash
Speed
Green Fast
Receptacle
Identification
Remote user is requesting outlet identification.
The LED should stop flashing after 10 seconds.
Green Steady On
Input Voltage Supported
Receptacle Powered On
Normal Operation
Off NA Voltage Off
Check power source and input plug’s receptacle
wiring.
Check receptacle power control settings.
Red Steady On
Line Undervoltage
Alarm
Check power source for power quality problem. If
the MPH2 uses 3-phase power, a single low-
voltage phase may cause one or more
undervoltage alarms. The undervoltage alarm is
factory-set to -10% of the minimum input voltage
range on the nameplate; it cannot be changed.
Red Fast
Line or Receptacle
Overcurrent Alarm
Check for changing load conditions.
Check overcurrent alarm threshold settings.
Green Slow
Line or Receptacle
Overcurrent Warning
Check for changing load conditions.
Check overcurrent warning threshold settings.
Red Fast
Line or Receptacle
Undercurrent Alarm
Check for removal of load.
Check undercurrent alarm threshold settings.
Red
(All Receptacle
LED’s)
Pulse
Branch Circuit
Breaker Open
Check for changing load conditions; confirm circuit
breaker actuator is closed. If open, correct loading
condition before pressing circuit breaker actuator
closed again.
Green
(All Receptacle
LED’s)
Slow
Branch Overcurrent
Warning
Check for changing load conditions.
Check overcurrent warning threshold settings.
Red
(All Receptacle
LED’s)
Fast
Branch Overcurrent
Alarm
Check for changing load conditions.
Check overcurrent alarm threshold settings.