Indoor Air Systems Air Cleaner User Manual

11
TI-131
0105
Model 700ERV
®
CLEAN • FRESH • AIR
SPECIFICATIONS
LATENT RECOVERY (MOISTURE) TRANSFER CORES
Modular (2 section) enthalpic (moisture) transfer cores
arranged for efficient cross-flow ventilation.
MOTORS
Two PSC, 3 speed single shafted, 120 VAC, 2.75 Amps each
(5.5 total on high speed). HP - 1/10, 1625 RPM. Watts - total
on high speed - 648.
FILTERS
Washable air filters in exhaust and supply air streams.
BLOWERS
Centrifugal type rated at 700 CFM (329 L/s) free air delivery.
Each air stream has one single shafted motor driving a
centrifugal blower.
CONNECTION DUCT SIZES
Four - 14" x 8" (356 mm x 200 mm)
MOUNTING
Unit to be set on support brackets hung by threaded rod type
apparatus (brackets and rods not provided).
CASE
20 gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated with foil faced insulation
where required to prevent exterior condensation.
CONTROLS
Illuminated power switch, 3 speed blower control, low voltage
(24 VAC) terminals for connection of remote controls.
WEIGHT 142 lbs (64.4 kg) SHIPPING WEIGHT 167 lbs. (75.8 kg)
OPTIONS
99-101 Sixty Minute Remote Timer
All units conform to CSA and UL standards.
WARRANTY
Units carry a 5 year warranty on the energy recovery cores
and 2 year replacement parts warranty.
ERVs are not recommended for regions where the design
temperature is below 25°F (-4°C)
AIRFLOWS (Each Air Stream)
423 (900)
378 (800)
329 (700)
282 (600)
235 (500)
190 (400)
143 (300)
94 (200)
42 (100)
AIRFLOW L/s (CFM)
25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)
EXTERNAL STATIC PRESSURE IN PASCALS (IN. W.C.)
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
5.5 HIGH
4.7 LOW
70%
60%
50%
143
(300)
190
(400)
235
(500)
282
(600)
329
(700)
TEMPERATURE EFFECTIVENESS
AIRFLOW IN L/s (CFM)
NOTE: Exhaust Relative Humidity (RH) at 40%
EFFECTIVENESS
HIGH SPEED
MED SPEED
LOW SPEED
5.0 MED
PERFORMANCE
29 5/8"
(753 mm)
8"
(200 mm)
FRONT VIEW
24 5/8 "
(625 mm)
28 3/4"
(730 mm)
14"
(356 mm)
8 1/4"
(210 mm)
INLET SIDE
DIMENSIONS 700ERV
inches (mm)
8"
(200 mm)
28 3/4"
(730 mm)
14"
(356 mm)
6 1/4"
(159 mm)
MOUNTING POINTS
CONTROLS
DISCHARGE SIDE
EXHAUST AIR
TO OUTSIDE
EXHAUST AIR
FROM BUILDING
SUPPLY AIR
TO BUILDING
SUPPLY AIR
FROM OUTSIDE
NOTE: 
Service clearance
is 30 in. (760 mm)
HEAT RECOVERY VENTILATORS (HRVs)
¤
6 1/2"
(165 mm)
6 1/2"
(165 mm)
ENTHALPIC CORE
DATE: __________________________
PROJECT: ________________________________________
MECHANICAL CONTRACTOR: ________________________________
511 McCormick Blvd.
London, Ontario
N5W 4C8
Ph: (519) 457-1904
Fx: (519) 457-1676
Email: nutech@lifebreath.com