User Guide

Troubleshooting
15
CAUSE SOLUTION
SYMPTOM
Poor Air Flows
Supply air feels cold
Dehumidistat is not Operating
Humidity Levels are too High, during the
winter months Condensation is appearing
on the windows
Humidity Levels are too Low
ERV and / or Ducts Frosting up
Condensation or Ice Build Up in Insulated
Duct to the Outside
1/4” (6 mm) mesh on the outside hoods is plugged
filters plugged
core obstructed
house grilles closed or blocked
dampers are closed if installed
poor power supply at site
ductwork is restricting ERV
improper speed control setting
ERV airflow improperly balanced
poor location of supply grilles, the airflow may
irritate the occupant
outdoor temperature extremely cold
outdoor temperature is above 15°C (59°F)
improper low voltage connection
external low voltage is shortened out by a staple or nail
check dehumidistat setting it may be on OFF
dehumidistat is set too high
lifestyle of the occupants
moisture coming into the home from an unvented
or unheated crawl space
moisture is remaining in the washroom and kitchen areas
condensation seems to form in the spring and fall
ERV is set at too low a speed
dehumidistat control set too low
blower speed of ERV is too high
lifestyle of occupants
ERV airflows may be improperly balanced
ERV airflows are improperly balanced
malfunction of the ERV frost prevention system
incomplete vapor barrier around insulated duct
a hole or tear in outer duct covering
clean exterior hoods or vents
remove and clean filter
remove and clean core
check and open grilles
open and adjust dampers
have electrician check supply voltage at house
check duct installation
increase the speed of ERV
have contractor balance ERV
locate the grilles high on the walls or under the baseboards,
install ceiling mounted diffuser or grilles so as not to directly
spill the supply air on the occupant (eg. over a sofa)
turn down the ERV supply speed. A small duct heater
(1kw) could be used to temper the supply air
placement of furniture or closed doors is restricting the
movement of air in the home
if supply air is ducted into furnace return, the furnace fan
may need to run continuously to distribute
ventilation air comfortably
dehumidistat is functioning normally (see Auto Dehumidistat
Disable in this manual)
check that the correct terminals have been used
check external wiring for a short
set the dehumidistat at the desired setting
set dehumidistat lower
avoid hanging clothes to dry, storing wood and venting clothes
dryer inside. Heating wood may have to be moved outside
vent crawl space and place a vapor barrier on the floor
of the crawl space
ducts from the washroom should be sized to remove moist
air as effectively as possible, use of a bathroom fan for
short periods will remove additional moisture
on humid days, as the seasons change, some condensation
may appear but the homes air quality will remain high
with some ERV use
increase speed of the ERV
set dehumidistat higher
decrease ERV blower speed
humidity may have to be added through the use of humidifiers
have a contractor balance ERV airflows
have HVAC contractor balance the ERV
ensure damper defrost is operating during self-test
tape and seal all joints
tape any holes or tears made in the outer duct covering
ensure that the vapor barrier is completely sealed
Excessive vibration
Dirt on fan wheels
Have a contractor service ERV