Submittal Sheet

_
_
Qty:
_
_
_
Date:
Tag:
Project:
Engineer:
_
Contractor:
Supplier:
Quote #:
Submitted By
_
_
_
All u
nits conform to CSA and UL standards
30 ERV
ENERGY RECOVERY VENTILATOR
ENGINEERING DATA
TOTAL RECOVERY CORE
The cross-flow energy recovery core transfers heat and water vapor between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each airstream has an independent motorized impeller, with multiple fan speed
operation.
FILTERS
Washable pre filters in exhaust and supply airstreams.
MOUNTING THE ERV
Hanging straps supplied with the unit.
FROST PREVENTION
Temperature sensor activated, periodically shuts down supply motor. Drains not
required.
CASE
20 gauge prepainted galvanized steel for superior corrosion resistance, insulated to
prevent exterior condensation.
INSTALLER SELECTABLE HIGH SPEED SETTINGS
The highest speed, "H3" is the factory setting. Installers may select a lower high speed
on set up. See chart for airflows H1, H2, and H3.
ELECTRONICS
The main control can be wall mounted in a central location. 3 wire 20 gauge (min.) 100 ft
length (max.).
CONTROL OPTIONS
Sensible Efficiency:
Thermal
Total Efficiency:
Moisture and Thermal
@95F
Effectiveness:
Based on temperature differential between
the 2 airstreams
Efficiency:
Takes into account all power inputs
and leakage
WEIGHT 33 lbs (15 kg) SHIPPING WEIGHT 36 lbs (16 kg)
DIMENSIONS 30 ERV
NOTE: All specifications are subject to change without notice.
TIMER OPTIONS
99-DET01 Lifebreath 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes.
3 wire connection.
99-DET02 WIRELESS Lifebreath 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or
60 minutes. Wirelessly connects to main control for ease of installation. 40' approximate range.
99-RX02 WIRELESS Repeater - Used to extend range of 99-DET02 Wireless Timers. Plugs into 120V
power outlet. Wirelessly connects to main control and 99-DET02. Install at halfway point between
timer and main wall control if timer is out of range.
ACCESSORY OPTIONS
99-163 Duct Heater w/Electronic SCR Thermostat - 1 kW, 6 in (152 mm)
99-184 Weatherhoods - Two 4 in (102 mm)
99-194 4" Dual Hood - One 6 in (152 mm) opening for supply and exhaust.
99-080-04 Wall Mounting Kit
Max. Temperature Recovery
78%
Sensible Effectiveness
@ 55 cfm (26 L/s)
32°F (0°C )
78%
Sensible Efficiency
@ 55 cfm (26 L/s)
32°F (
0°C )
70%
Total Efficiency
@ 63 cfm (30 L/s)
95°F (35°C )
48%
VAC @ 60Hz 120
Amp rating
0.48
Watts - High Speed 57
Watts - Low Speed
44
@ 0.1
in
(25 P a)
@ 0.2
in
(50 P a)
@ 0.3
in
(75 P a)
@ 0.4
in
(100 P a)
@ 0.5
in
(125 P a)
@ 0.6
in
(150 P a)
@ 0.7
in
(175 P a)
72 cfm (34 L/s)
68 cfm (32 L/s)
63 cfm (30 L/s)
57 cfm (27 L/s)
50 cfm (24 L/s)
43 cfm (20 L/s)
36 cfm (17 L/s)
External Static Pressure
Airflow
Performance
Net supply airflow in cfm (L /s) against external static pressure
20
30
40
50
60
70
80
0 0.1 0.2 0.6 0.7
0.8
Airflow (cfm)
HI 2
HI 1
LOW
HI 3
0.3 0.4
0.5
Static Pressure (in w.g.)
Front View
Top View
Fresh Air
From Outside
Stale Air To
Outside
Fresh Air To
Inside
Stale Air
From Inside
18 3/4" (476 mm)
17 7/8" (454 mm)
19 1/4" (489 mm)
Note: Front
clearance of 25
in. (635
mm) is
recommended
for servicing unit.
All ducts use 4
in. (102 mm)
round collars,
balancing
dampers are in
each air stream.
99-DXPL02 Lifebreath Digital Control
5 speed operation on each mode
Humidity control through adjustable
Dehumidistat
5 user selectable operational modes: Continuous
Ventilation, Continuous Recirculation, 20 ON/40
OFF, 10 ON/50 OFF, 20 ON/40 Recirculation
20/40/60 min. High speed override button
Compatible with 99-DET02 Wireless Timers
3 wire connection
99-BC04 Lifebreath Ventilation Control
2 speed fan setting (Low/High)
2 modes of operation: Ventilation, 20/40
Compatible with 99-DET02 Wireless
Timers
3 wire connection
WARRANTY
5 year warranty on the E