Install Instructions

Drain Connection
Drain Connection
The HRV may produce some condensation during a
defrost cycle. This water should flow into a nearby
drain, or be taken away by a condensate pump.
The HRV cabinet has a pre-punched hole for the
drain. Insert the drain spout through the hole in the
drain pan. Be sure to install the "O ring" which seals
each spout to the pan. HAND TIGHTEN the washer
and lock nut which hold the drain spout in place.
Make a loop in a length of 1/2" drain hose to
construct a P-Trap (drain hose not included). Ensure
that the loop is large enough to avoid kinks and
secure it with a zip tie (zip tie not included). Pour a
cup of water into the drain pan of the HRV after the
drain connection is complete. This creates a water
seal that prevents odors from being drawn up the
hose and into the fresh air supply of the HRV.
The HRV and all condensate lines must
be installed in a space where the
temperature is maintained above the
freezing point or freeze protection must be
provided.
CAUTION
Drain Spout
O Ring
Pre-punched hole located in
bottom center of HRV/ERV
P-Trap
Zip Tie
(not included)
1/2" Drain Hose
(not included)
To Drain or Condensate Pump
Drain trap and tubing MUST be
below bottom of door with 1/4"
per foot downwards slope away
from unit.
CAUTION
Note: Secondary drain pan may be required to
protect from condensate leakage.
DRAIN HOSE PLUMBING
22