Submittal Sheet

Table Of Contents
RNC4-TPD Performance
(HVI certified)
Net supply airflow in cfm against external static pressure
External Static Press re
Airflow
Max. Temperature Recovery
78%
Sensible Eecveness
@ 47 cfm (22 L/s)
32°F (0°C )
78%
Sensible Eciency
@ 47 cfm (22 L/s)
32°F (
0°C )
70%
Sensible Eciency
@ 52 cfm (24.5 L/s)
-13°F (-25°C )
65%
VAC @ 60Hz 120
Amp rang
0.48
Sensible Efficiency: Thermal
Effectiveness: Based on temperature differential between
the two airstreams
Efficiency: Takes into account all power inputs
RNC4-TPD
HEAT RECOVERY VENTILATOR
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The counter-flow heat recovery core transfers heat between the two airstreams. It is
easily removed for cleaning or service.
MOTORS AND BLOWERS
Each airstream has an independent motorized impeller with multiple fan speed operations.
FILTERS
Washable air filters in exhaust and supply airstreams.
MOUNTING THE HRV
“S” hooks and hanging straps supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
20 gauge prepainted galvanized steel for superior corrosion resistance, insulated to prevent
exterior condensation. Drain connections: Two 1/2 in (12 mm) OD.
Balancing ports are located on unit.
INSTALLER SELECTABLE HIGH SPEED SETTINGS
Adjustable DIP switches are located on the circuit board, Hi3 is the factory setting.
Refer to the Installation manual for the adjustment instructions.
ELECTRONICS
The optional controls can be wall mounted in a central location of the home. 3 wire 20 gauge
(min.) 100 ft length (max.).
CONTROL OPTIONS
WEIGHT 35 lbs (16 kg) SHIPPING WEIGHT 38 lbs (17 kg)
DIMENSIONS RNC4-TPD
Units carry a lifetime warranty on the HRV
core and a 5 year replacement parts
warranty.
_
_
Qty:
_
_
_
_
_
_
_
Date:
Tag:
Project:
Engineer:
Contractor:
Supplier:
Quote #:
Submi ed By:
All units conform to CSA and UL standards
Hex Core - Recirculating
70 cfm (33 L/s)
64 cfm (30 L/s)
58 cfm (27 L/s)
@ 0.2 in (50 Pa)
@ 0.3 in (75 Pa)
@ 0.4 in (100 Pa)
@ 0.5 in (125 Pa)
53 cfm (25 L/s)
NOTE: All specifications are subject to change
without notice.
Watts - High Speed 57
Watts - Low Speed
38
74 cfm (35 L/s)@ 0.
1 in (25 Pa)
HI 3
HI 2
HI 1
LOW
ACCESSORY OPTIONS
99-163 Duct Heater w/Electronic SCR Thermostat - 1 kW, 6 in (152 mm)
99-99-184 Weatherhood - Two 4 in (102 mm)
99-194 4" Dual Hood - One 6 in (152 mm) opening for supply and exhaust.
99-080-04 Wall Mount Bracket
18 3/4" (476 mm)
19 1/4" (489 mm)
Note: Front
clearance of 25 in
(635 mm) is
recommended for
servicing unit. All
ducts use 4 in (102
mm) round collars,
balancing dampers
are located in all air
streams.
17 7/8" (454 mm)
Top View
Front View
TIMER OPTIONS
99-DET01 Lifebreath 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes.
99-BC03 Lifebreath Ventilation Control
Continuous Low fan speed
Humidity control through adjustable
Dehumidistat
3 modes of operation: Ventilation,
Recirculation, 20/40
Compatible with 99-DET02 Wireless Timers
3 wire connection
99-DXPL02 Lifebreath Digital Control
5 speed operation on each mode
Humidity control through adjustable
Dehumidistat
5 user selectable operational modes: Continuous
Ventilation, Continuous Recirculation, 20 ON/40
OFF, 10 ON/50 OFF, 20 ON/40 Recirculation
20/40/60 min. High speed override button
Compatible with 99-DET02 Wireless Timers
3 wire connection
99-BC02 Lifebreath Ventilation Control
2 speed fan setting (Low/High)
Humidity control through adjustable
Dehumidistat
Compatible with 99-DET02 Wireless Timers
3 wire connection
between timer and main wall control if timer is out of range.
99- BC04 Lifebreath Ventilation Control
2 speed fan setting (Low/High)
2 modes of operation: Ventilation, 20/40
Compatible with 99-DET02 Wireless
Timers
3 wire connection
99-DH01 Lifebreath Dehumidistat
Humidity control through adjustable
Dehumidistat
3 wire connection
3 wire connecon.
99-DET02 Lifebreath WIRELESS 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60
minutes. Wirelessly connects to main control for ease of install ation. 40' approximate range.
99-RX02 Lifebreath WIRELESS Repeater - Used to extend range of 99-DET02 Wireless Timers. Plugs into
120V power outlet. Wirelessly connects to main control and 99-DET02. Install at halfway point