User Manual

Standby Voltage = 12 to 24VDC
A wall-mount transformer is
provided. Loss of power or data
will result in a Trouble Condition
at the FACP
Baud Rate = 9600
Bits = 8
Stop = 1
Parity = 0
Selectable for RS-232 or RS-485
data
Temperature: 32° to 100°F
Humidity: Non-condensing
Current: 125 ma.
The LCD-240 was designed for use on a fire alarm system printer port. The
unit displays the same information the would be printed on a printer. When em-
bedded in a Graphic Map, the LCD-240/G provides complete annunciation
without using LEDs or lamps.
Each alarm initiating device will be shown on the graphic map, along with its
corresponding address. When an alarm occurs, the unit will display the alarm
addresses, and a descriptive message. The address shown on the LCD dis-
play is then correlated to the device location on the map.
Technical Specifications
General Description
109 Portwatch Way Wilmington, N.C. 28412 Phone: (800) 251-2512 Fax: (800) 251-9878
Internet: www.ledinc.com Email: sales@ledinc.com
Graphic Annunciators * Water Leak Detection
Fireman’s Smoke Control Panels * ARA Systems