- Varec Radar Tank Gauge Model 7532 RTG Installation & Operations Manual

49
7532 Commissioning
6.4 Basic Setup with the VU 331
Function "measured value" (000)
This function displays the current measured value in the selected unit
(see "customer unit" (042) function). The number of digits after decimal point can be
selected in the "no.of decimals" (095) function. The length of the bargraph corresponds
to the percentile value of the present measured value with regard to the span.
6.4.1 Function group "basic setup" (00)
Function "tank shape" (002)
This function is used to select the tank shape.
Note!
For the application of the 7532 RTG the selection "stilling well" has to be chosen in the
function "tank shape" (002).
Selection:
dome ceiling
horizontal cyl
•bypass
stilling well
flat ceiling (Typical ceiling of storage tanks: a slight slope of only a few degrees can
be neglected.)
•sphere
E
+
E
+
E
+
L00-FMR2xxxx-14-00-00-en-007