- Varec Radar Tank Gauge Model 7532 RTG Installation & Operations Manual

51
7532 Commissioning
Function "process cond." (004)
This function is used to select the process conditions.
Selection:
standard
calm surface
•turb. surface
agitator
fast change
test:no filter
Note!
The phase evaluation of the 7500 RTG (see »Function "auto-correction" (031)« on
page 57) is only activated if you select the measuring conditions "standard" or
"calm surface". We strongly recommend that, in the case of rough product surfaces or
rapid filling, you activate the appropriate application parameters.
E
+
standard calm surface
For all applications that do
not fit into any of the
following groups.
Storage tanks with immersion
tube or bottom filling
The filter and output
damping are set to average
values.
The averaging filters and
output damping are set to
high values.
-> steady meas. value
-> precise measurement
-> slower reaction time