 AB-0602A ARCHITECTURAL BALLAST DRIVER 
 Version 0.10  OWNERS MANUAL   07/05/2012 
www.lightronics.com 
Lightronics Inc.  509 Central Drive  Virginia Beach, Va  234354    757 486 3588
DESCRIPTION AND FEATURES 
The AB-0602A is a 6 circuit, 2400 Watts per circuit 
ballast driver intended for dimmable fluorescent and 
LED fixtures which use a switched 120VAC hot 
feed and dimmed 120VAC control signal to operate 
them. A three circuit version (AB-0302A) is also 
available and operates identically. 
The AB-0602A can also be used as a conventional 
relay pack by using only the switched hot feed 
controls without the dimmed 120VAC signal. 
EXTERNAL CONTROLS 
The AB-0602A can communicate with remotely 
located control equipment in several ways. 
A USITT DMX-512 protocol bus is provided so the 
unit may be used with any DMX lighting console.  
The AB-0602A is fully patchable with respect to the 
DMX bus. 
The AB-0602A may also be controlled by several 
types of wall mounted smart remote stations. Smart 
remotes communicate with the unit by way of a low 
voltage RS-485 bus. This bus is completely separate 
from the DMX bus. Smart remotes are used to 
activate preset scenes which have been stored in the 
AB-0602A. There are several types of smart remote 
stations. Multiple smart remotes of the same or 
different types may be chained together on the RS-
485 bus. The same RS-485 bus may be chained to 
multiple AB-0602A units. 
The AB-0602A may additionally be controlled by an 
arrangement of one or more momentary switches 
(simple remotes). The switches may be used to 
control a specific set of eight scenes which are 
stored in the AB-0602A.
INSTALLATION 
PHYSICAL LOCATION 
The unit is intended for 
INDOOR USE ONLY
 and 
should not be subjected to excessive moisture or 
heat. The AB-0602A is designed to be wall 
mounted in a equipment room or electrical 
distribution area.. The ambient air in the installation 
area should be below 86 deg F. Provide spacing 
between the unit and other equipment to allow air 
flow around the unit. See the 
DIMENSIONS AND 
LOCATIONS
 diagram for more location information. 
POWER REQUIREMENTS 
TURN OFF ALL POWER SOURCES BEFORE 
MAKING CONNECTIONS 
The internal AB-0602A circuitry requires a 120VAC 
line feed. The circuitry is fused with a 1/2 Amp fast 
acting 1 1/4" x 1/4", 250V fuse. 
LINE IN CONNECTIONS 
A separate 120 VAC line in feed is needed for each 
of the loads (A - F). The maximum current for each 
feed circuit is 20 Amps. The diagram 
DIMENSIONS 
AND LOCATIONS
 shows the connection details. A 
grounding bar is also provided. 
SWITCHED HOTS CONNECTIONS 
Switched hot connections are made on a terminal 
strip inside the AB-0602A. The diagram 
DIMENSIONS AND LOCATIONS
 shows the 
connection details. 
DIMMED HOT OUTPUT CONNECTIONS 
Dimmed hot connections are made on a terminal 
strip inside the AB-0602A. The maximum load is 1 
Amp. per circuit. The diagram 
DIMENSIONS AND 
LOCATIONS
 shows the connection details. 
CONTROL SIGNAL CONNECTIONS 
Connectors with screw down terminals are provided 
for connection to DMX consoles, smart remotes, and 
simple remote stations. Specific wiring connection  
information for all external control signals is shown 
in the 
CONTROL SIGNAL CONNECTIONS 
diagram.
DANGER 
RISK OF FIRE 
DANGER 
RISK OF ELECTRIC SHOCK 