THREE PHASE POWER INPUT CONNECTIONS 
Factory Supplied Configuration 
BLA
CK
COLOR 
CODED 
SHRINK 
TUBING 
BLACK 
BLUE 
BLACK 
RED 
RED 
RED 
BLUE 
3 PHASE 
120/208VAC 
20A EACH/LINE 
L1
L2 
L3 
 NEUT 
SINGLE PHASE POWER CONNECTIONS 
The DB-612 may be field converted to accommodate a SINGLE PHASE 120/240 power service. Consult the 
applicable electrical codes for your location for exact wire specifications. The unit must be powered from a circuit 
providing a minimum of 30 Amps per line (2 pole 30 Amp circuit breaker). The minimum wire size is AWG#10.  
Wire may be either stranded or solid. The terminals are intended for copper wire only. 
MAKE CERTAIN THAT THE INPUT POWER SOURCE IS 
DE-ENERGIZED BEFORE MAKING CONNECTIONS. 
1  Remove the access cover at the end of the unit. 
2  Connect the 2 "HOT" power input wires to the L1 and L3 terminals. 
Note that the terminal marked L2 is not used for single phase operation. 
3  Connect the neutral wire to the terminal marked N. 
4  Connect a ground wire to the CHASSIS GROUND terminal marked G. 
There are two blue wires in the L2 terminal on the opposite side of the power input terminal strip. These wires 
have color coded shrink tubing markers on them. One of them is marked with BLACK. The other is marked with 
RED. 
5  Move the BLUE wire with the BLACK marker from the L2 terminal to the L1 terminal. 
6  Move the BLUE wire with the RED marker from the L2 terminal to the L3 terminal. 
A diagram of single phase power connections is shown below : 
SINGLE PHASE POWER INPUT CONNECTIONS 
L1 
SINGLE PHASE 
120/240VAC 
30A EACH LINE 
BLUE 
BLACK 
BLACK 
BLACK 
BLUE 
RED 
RED 
RED 
 NEUT 
 L2 NOT USED 
L3 
COLOR 
CODED 
SHRINK 
TUBING 