Instruction Manual
    Page 1 of 5 
FL-4020 FLUORESCENT BALLAST CONTROLLER 
 Version 1.0  OWNERS MANUAL             10/06/2005 
www.lightronics.com 
Lightronics Inc              509 Central Drive Virginia Beach, VA 23454         Tel 757 486 3588 
PRODUCT DESCRIPTION 
The FL-4020 is a four channel controller add on product for the AR-1202 Architectural dimmer. It provides control 
of dimmable fluorescent lighting ballasts. The FL-4020 provides four 2400 Watt channels of fluorescent dimming 
which is interfaced to the AR-1202 control circuitry. The AR-1202 uses its four auxillary channels (13 – 16 ) to 
control the FL-4020. Dual SCR “zero crossing” switching is used to control the switched hot lines. 
The FL-4020 is supplied in two versions: 
FL-4020A: Controls ballasts which use a switched 120 VAC “hot” and a dimmed 120 VAC as a control signal. 
FL-4020D: Controls ballasts which use a switched 120 VAC “hot” and a 0-10 VDC dimming control signal. 
INSTALLATION 
W
ARNING 
MAKE CERTAIN POWER IS REMOVED FROM THE FEED CIRCUITS 
BEFORE YOU BEGIN INSTALLATION. 
The unit should be wall mounted close to an AR-1202 dimmer. The unit may be "stood off" from the wall (aprox. 
1") to assure clear airflow across the rear heat sink surface. A 120VAC 20 Amp power input must be provided for 
each dimming channel. Each channel may control multiple ballasts as long as the channel load does not exceed 
2400 Watts. The internal low current electronic circuitry is powered, via a 1/2 Amp 250VAC fast blow fuse, by the 
H1 input power connection. 
REQUIREMENTS FOR THREE PHASE OPERATION: 
In order to provide zero crossing switching, the AR-1202 uses a specific phase sequence when operated with 3 
phase power. The sequence convention must also be adhered to when connecting the FL-4020. The phase 
connected to the AR-1202 H1 power input terminal must also be used for channels 1 and 4 of the FL-4020. The 
AR-1202 H2 phase must be used for FL-4020 channel 2. The AR-1202 H3 phase must be used for FL-4020 
channel 3. The table below summarizes this requirement. 
POWER PHASE 
A
R-1202 CHANNEL FL-4020 CHANNEL 
H1 13 13
H2 14 14
H3 15 15
H1 16 16
TYPICAL CONNECTION SCHEME 
SWITCHED 120VAC 
SWITCHED 120VAC 
SWITCHED 120VAC 
SWITCHED 120VAC 
Control Signal 
Control Signal 
Control Signal 
Control Signal 
CH 13 
CH 16 
CH 15 
CH 14 
Channel 16 Control 
Channel 15 Control 
Channel 14 Control 
Channel 13 Control 
AR-1202 
User supplied 
120VAC feeds from 
circuit breaker 
p
anel 
To 
Lamp 
Ballasts 
FL-4020 
 Control Signal may be either 0 - 10 VDC 
OR 
120VAC Dimmed hot 






