User's Manual
Page 16 of 44
© 2020 LINAK A/S
Troubleshooting for Parallel
Symptom Possible cause Action
Actuators run in smaller steps
before stop
Insufficient power supply Check the power supply while the actuator is running
Connect the actuator(s) to BusLink one at a time and check
the following:
- Reason for last stop (page 62)
- Current cut-off levels in both
directions
After everything is connected, put power on all actuators at
the same time. Then wait 10 seconds before the Run In/Run
Out signals are activated
Signal cable damaged or
removed under operation
All actuators stop at the same position The signal and power cables MUST be re-connected to all
actuators.
Ensure that no actuator is missing in the system.
Otherwise, the system will not work, not even after
re-powering
Please see non-critical info below
After everything is connected, put power on all actuators at
the same time. Then wait 10 seconds before the Run In/Run
Out signals are activated