Owner manual

A-6
INSTALLATION
RANGER® 225
A-6
120/240 VOLT DUAL VOLTAGE RECEPTACLE
The 120/240 volt receptacle can supply up to 38
amps of 240 volt power to a two wire circuit, up to 38
amps of 120 volts power from each side of a three
wire circuit (up to 76 amps total). Do not connect the
120 volt circuits in parallel. Current sensing for the
automatic idle feature is only in one leg of the three
wire circuit as shown in the following column.
120 V DUPLEX RECEPTACLES
The 120V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs.
The current rating of any plug used with the system
must be at least equal to the current load through the
associated receptacle.
MOTOR STARTING
Most 1.5 hp AC single phase motors can be started if
there is no load on the motor or other load connected
to the machine, since the full load current rating of a
1.5 hp motor is approximately 20 amperes (10
amperes for 240 volt motors). The motor may be run
at full load when plugged into only one side of the
duplex receptacle. Larger motors through 2 hp can be
run provided the receptacle rating as previously stated
is not exceeded. This may necessitate 240V operation
only.
GND
120 V
120 V*
240 V
*Current Sensing for Automatic Idle.
(Receptacle viewed from front of Machine)
RANGER® 225 Extension Cord Length Recommendations
(Use the shortest length extension cord possible sized per the following table.)
WELDER OPERATION
WELDER OUTPUT
Maximum Open Circuit Voltage at 3700 RPM is 80
Volts RMS.
Duty Cycle is the percentage of time the load is
being applied in a 10 minute period. For example, a
60% duty cycle represents 6 minutes of load and 4
minutes of no load in a 10 minute period. Duty
Cycle for the RANGER® 225 is 100%.
AUXILIARY POWER
The RANGER® 225 can provide up to 9,000 watts of
120/240 volts AC, single phase 60Hz power for con-
tinuous use, and up to 10,500 watts of 120/240 volts
AC, single phase 60Hz power peak use. The front of
the machine includes three receptacles for connecting
the AC power plugs; one 50 amp 120/240 volt NEMA
14-50R receptacle and two 20 amp 120 volt NEMA 5-
20R receptacles. Output voltage is within +/-10% at all
loads up to rated capacity.
All auxiliary power is protected by circuit breakers. the
120V has 20 Amp circuit breakers for each duplex
receptacle. The 120/240V Single Phase has a 40 Amp
2-pole Circuit Breaker that disconnects both hot leads
simultaneously.
Do not connect any plugs that connect to the
power receptacles in parallel.
------------------------------------------------------------------------
Start the engine and set the “IDLER” control switch to
the desired operating mode. Set the “CONTROL” to
10. Voltage is now correct at the receptacles for auxil-
iary power.
CAUTION
Current
(Amps)
15
20
15
20
38
Voltage
Volts
120
120
240
240
240
Load
(Watts)
1800
2400
3600
4800
9000
14 AWG
30 (9)
60 (18)
12 AWG
40 (19)
30 (9)
75 (23)
60 (18)
10 AWG
75 (23)
50 (15)
150 (46)
100 (30)
50 (15)
8 AWG
125 (38)
88 (27)
225 (69)
175 (53)
90 (27)
6 AWG
175 (53)
138 (42)
350 (107)
275 (84)
150 (46)
4 AWG
300 (91)
225 (69)
600 (183)
450 (137)
225 (69)
Conductor size is based on maximum 2.0% voltage drop.
Maximum Allowable Cord Length in ft. (m) for Conductor Size
RANGER® 225
Constant Current 210 Amps DC @ 25 Volts
Constant Voltage 200 Amps DC @ 20 Volts