User Guide

Set Operating Current
To set the operating current, configure SW1, SW2, SW3, SW4 from DIP switch
If the Lucid Connected Home Charging Station is installed on a breaker smaller than 100A, the dip
switches support de-rating the station to match said breaker. This same table below can also be
found on a sticker inside the station for ease of use.
Note: Power must remain off before setting or configuring the DIP switch.
Item Continuous Output Configure Circuit Breaker Size**
DIP Switch Configuration
6A 1 2 3 4 7.5A
UP
DOWN
12A 1 2 3 4 15A
UP
DOWN
16A 1 2 3 4 20A
UP
DOWN
20A 1 2 3 4 25A
UP
DOWN
24A 1 2 3 4 30A
UP
DOWN
28A 1 2 3 4 35A
UP
DOWN
32A 1 2 3 4 40A
UP
DOWN
36A 1 2 3 4 45A
UP
DOWN