Specification

®
SPECIFICATIONS
ORDERING INFO
OPTIONS
LOW VOLTAGE RELAY (R)
Enables sensors to interface with
other systems (e.g., BMS, lighting
panels)
Provides dry contact closure via a
SPDT, 1 Amp, 40 Volt relay
Only one relay needed per zone
Changes state when all connected
sensors register unoccupied
Relay requires sensor power to
function
OCCUPANCY CONTROLLED
DIMMING (D)
Provides dimming output to control
0-10 VDC dimmable ballasts
Provides a second occupancy time-
out period that enables the lights to go
to a dim setting before turning off
Adjustable max/min dim setting
Only one sensor per zone needs to
have dimming output
PHOTOCELL (P)
Auto set-point calibration
Two selectable modes of operation
On/Off mode: Photocell has full
control during periods of occupancy
Inhibit mode: Photocell can prevent
lights from turning on if adequate
daylight is available, but cannot turn
lights off
PHOTOCELL W/ DIMMING (ADC)
Photocell within sensor maintains total
room light level by controlling levels of
0-10 VDC dimmable ballasts
Photocell also has full on/off control
during periods of occupancy
Provides a second occupancy time-
out period that enables the lights to go
to a dim setting before turning off
Note: LampMaximizer+ features not
available with ADC option
LOW TEMP/HIGH HUMIDITY (LT)
Sensor is corrosion resistant to
moisture
• Operates down to -40º F/C
OVERVIEW
The CM 9 Series occupancy sensor offers
amazing performance and sensitivity to small
motions for a standard range Passive Infrared
(PIR) sensor. Ideal for small rooms with drop
ceilings and areas without obstructions, the
CM 9 is a snap to install. Its light weight allows
surface mounting to drop ceilings or a ceiling
grid. The CM 9 sensor can cover entire private
ofces or smaller rooms by itself, however it is
also the ideal lead sensor for odd shaped rooms.
For example, a CM 9 in a restroom vestibule
can communicate with a CM PDT 9 Dual
Technology sensor in a main stall area. Another
application is a CM 9 covering an entrance hall
to a classroom and communicating with a WV
PDT 16 sensor covering the main room. In both
cases the lights would be activated on by the
CM 9. For mounting above 15 ft (4.57 m), see
the CM 6 Technical Data Sheet.
SENSOR OPERATION
The sensor detects changes in the infrared
energy given off by occupants as they move
within the eld-of-view. When occupancy is
detected, a DC output goes high and can
drive up to 200 mA of connected load. The
sensor is powered with 12-24 VAC/VDC and
typically operates with a PP20 or MP20 power
pack, enabling complete 20 Amp circuits to be
controlled. This innovative sensor requires no
eld calibration or sensitivity adjustments.
LAMPMAXIMIZER
®
This sensor also contains patent pending
LampMaximizer technology that allows users
to aggressively target energy savings while still
protecting lamp life. A minimum on timer, factory
set at 15 minutes, helps preserve lamp life by
eliminating all lamp cycles shorter than lamp
manufacturer recommendations.
A standard occupancy time delay is also present
that ensures lights turn off (assuming minimum
on timer has elapsed) if no occupancy is
detected. This timer is factory set at 10 minutes
to promote energy savings, but is adjustable
between 30 seconds and 20 minutes. These
adjustments can be done manually, through
the unit’s push-button, or automatically every
two weeks through an advanced mode, called
LampMaximizer+, that determines the optimum
time delay in order to maximize both lamp life
and energy savings. Additionally, this sensor
maintains statistics on total lamp on time and
number of cycles.
STANDARD RANGE 360º SENSOR
CEILING MOUNT • LOW VOLTAGE • PASSIVE INFRARED (PIR)
CM 9
FEATURES
100% Digital PIR Detection,
Excellent RF Immunity
360º Coverage Pattern
Push-Button Programmable
User Adjustable Time Delays
No Field Calibration or Sensitivity
Adjustments Required
Convenient Test Mode
100 hr Lamp Burn-in Timer
Green LED Indicator
LAMPMAXIMIZER
®
TECHNOLOGY
Protects Lamp Life while
Maximizing Energy Savings
Minimum On Timer (15 min default)
Occ. Time Delay (10 min defatult)
LampMaximizer+ Mode -
Optimizes Lamp Life & Energy
Savings (disabled by default)
Switch Counter (in 1000’s)
Total Lamp On Time (in khrs)
PHYSICAL SPECS
SIZE 4.55” Dia. (11.56 cm)
1.55” Deep (3.94 cm)
WEIGHT 6 oz
MOUNTING
Ceiling Tile Surface
3.5” Octagon Box
Single Gang Handy Box
COLOR White
ELECTRICAL SPECS
OPERATING VOLTAGE
12-24 VAC/VDC
CURRENT DRAW
Standard, 4 mA
w/ R option, 16 mA
DIMMING LOAD Sinks < 20mA;
~40 Ballasts @ .5mA each
RECOMMENDED POWER PACK
PP20
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
STORAGE TEMP
-14º to 160º F (-26º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
SILICONE FREE
ROHS COMPLIANT
RELAY
TEMP/HUMIDITY
Blank = None Blank = None Blank = Standard
R = Low Voltage Relay D = Occupancy Controlled Dimming LT = Low Temp
P = Photocell
ADC = Photocell w/ Dimming
CM 9 [RELAY] [DIMMING/PHOTOCELL] [TEMP/HUMIDITY]
DIMMING / PHOTOCELL CHOOSE ONE ONLY
C US LISTED
TITLE 24
MADE in U.S.A.
5 YEAR WARRANTY