Specification

900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a
period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material
Authorization number and repair or replace returned product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied
warranties (including the implied warranties of merchantability and tness for use) and under no circumstances shall
Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
TS-CMRB-001A
Revised 08.20.10 © 2010 Sensor Switch
INSTALLATION
WIRING (DO NOT WIRE HOT)
COVERAGE PATTERN
PROGRAMMING
Refer to instruction card IC7.001 for default settings and directions on programming the sensor via the push-button.
FB3
10 EXTENDED RANGE LENS
0 ft
9
0 m
2.7
28 21 14 7 0 ft 7 14 21 28
8.5 6.4 4.3 2.1 0 m 2.1 4.3 6.4 8.5
SIDE VIEW
TOP VIEW
28
14
0 ft
14
28
8.5
4.3
0 m
4.3
8.5
Best choice for large motion detection (e.g. walking)
Viewing angle of 67º in a 360º conical shaped pattern
Provides 28 ft (8.53 m) radial coverage when mounted to standard
9 ft (2.74 m) ceiling
7 to 15 ft (2.13 to 4.57 m) mounting heights provide 16 to 36 ft
(4.88 to 10.97 m) radial coverage
STANDARD WIRING
BLACK* - Line Input
BLACK* - Load Output
WHITE - Neutral
347 VAC OPTION (347)
Black wires are replaced w/ Red wires
DIMMING OPTIONS (D, ADC)
VIOLET - Connect to Violet control wire from 0-10 VDC
dimmable ballast
GRAY - Connect to Gray common wire from ballast
INITIAL POWER UP
The sensor’s relay is shipped in a latched closed position so the lights will
come on upon initial power-up. If the lights do not immediately turn on (initial
installation only) the latching relay opened during shipment and will close
within 30 secs.
Note: If the sensor loses power, the internal relay will latch to on.
VIO (+)
GRY (-)
[D, ADC] Dimming Options
PUSH BUTTON
LOCK NUTCHASE NIPPLE KNOCK OUT
The Fixture Mount Box enclosure has an extended chase nipple that is used
to mount the sensor through a ½” knockout hole to a xture or junction box.
Sensor will detect motions crossing segments more effectively than motions
parallel to beams.
If the sensor’s eld-of-view is partially blocked by the xture housing, the
FB3 Fixture Bracket (not included) can be used to lower the sensor down to
a level where its view is not impaired.
*BLACK wires can be reversed
}
*At 9ft Mtg.
A: When walking across beam, detection
will occur at approximately 28 feet. (8.53
m)
B: When walking into beam, detection will
occur at approximately 24 feet. (7.32 m)