Installation Sheet

INSTALLATION INSTRUCTIONS
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
Part #EMCSA00909 Rev. A
2017.01.05
One Lithonia Way, Conyers GA 30012
Phone: 800-334-8694
www.lithonia.com
SELF DIAGNOSTIC TESTING INSTRUCTIONS FOR
LED EXIT SIGN
NORMAL OPERATION: When unit is functioning properly with A.C. power supplied, the status indicator will be green and the EXIT
sign will be ON.
TESTING:
The exit performs two types of tests, Contingency and Non-Contingency. The contingency testing includes “Battery Discon-
nected Mode” and “LED Failure Mode”. When the Battery is disconnected, the indicator would indicate as Red (Steady). When a LED
fails, the indicator would indicate as Red (Blinking - three times). The Non-Contingency test is for testing the Battery for its “discharging”
and “recharging” capacity. A 30-second battery discharge test is performed every 30 days to check for the normal operation of the battery
and the unit. Also a full 90-minute discharge test is performed once a year to con rm the same. When the battery is in self-test mode,
the LED indicator would be ashing Green (One/Two/ Three Pulses). Upon completion of the test and after 24 hours battery charging
(Indicator on Red and Green ashing), the status indicator will return to either Green (Steady) indicating a properly functioning unit or Red
(Double Pulse) to show a battery failure. The following table shows the status indication.
MANUAL TESTING: Battery and ‘LED strip’ test may be manually initiated by pressing the test switch. Once the test switch is pressed,
the unit would be reset and the date of battery self-testing would start counting again.
OPERATION: During an electrical power failure, the LED strip will automatically come ON for a minimum of 90 minutes. To test this
unit, the battery needs to be charged at least for 24 hours before depressing the test switch (to do manual test). On pressing the test
switch, the LED strip will illuminate. The LEDs will turn OFF after 30 sec/30 min/90 min depending on the number of times the switch
has been pressed.
FUNCTION LED INDICATION FUNCTION LED INDICATION
EXIT is in Emergency Mode OFF Battery Failure Red (Flashing 2 times)
EXIT is in Normal Mode Green (Steady) Battery Recharge Failure Red (Flashing 1 time)
Battery Disconnected Red (Steady) 30-Second Battery Discharging Mode* Green (Flashing 1 time)
LED Failure Red (Flashing 3 times) 30-Minute Battery Discharging Mode** Green (Flashing 2 times)
Battery Charging Red and Green (Alternate Flashing) 90-Minute Battery Discharging Mode*** Green (Flashing 3 times)
*
Occurs once every 30 days ** Occurs once every 180 days *** Occurs once per year
ACTION REACTION & LED INDICATION
Push test button Once (within 2 seconds) 30-second test: Green light-Single blink
Push test button Twice (within 2 seconds) 30-minute test: Green light-Double blink
Push test button Thrice (within 2 seconds) 90-minute test: Green light-Triple blink
Push & Hold test button (for 6 seconds) Resets the xture from error mode

Summary of content (1 pages)