Installation Guide

SAVE THESE INSTRUCTIONS
1999 © Acuity Lighting Group, Inc., Rev A 07/24/07
RJ521318 INST SHT TFS
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
INSTALLATION
INSTRUCTIONS
RISK OF FIRE - Lamps are hot. Keep
combustible material away from hot
parts.
TROUBLESHOOTING
CAUTION
If this fixture fails to operate properly, check to
make sure:
The correct lamp is properly installed.
The fixture is wired correctly.
The lamp is not faulty.
The fixture is grounded correctly.
The line voltage at the fixture is correct.
Observe lamp manufacturer's recommendations
and restrictions on lamp operations, including but
not limited to ballast type, burning position, and
cycling. Use ANSI rated lamps only.
Maintenance: For optimum performance,
periodically clean reflector and lens with a soft,
damp cloth.
Important: DO NOT use abrasive materials, glass
cleaner or other solvents on lens or paint. Use only
mild, soapy water.
WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH,
INJURY, OR SIGNIFICANT PROPERTY DAMAGE
- For your protection, read and follow these warnings
and instructions carefully before installing or maintaining this fixture. These instructions do not attempt to
cover all installation and maintenance situations. If you do not understand these instructions or additional
information is required, contact Lithonia Lighting or your local Lithonia Lighting distributor.
WARNING: RISK OF ELECTRIC SHOCK - To avoid electric shock, serious injury, or death, be certain that
all electrical power is disconnected from the supply branch circuit conductors before installing or main-
taining this fixture. This product must be installed and maintained in accordance with the applicable instal-
lation codes by a person familiar with the construction and operation of the product and the hazards
involved.
WARNING: RISK OF PERSONAL INJURY - This product may have sharp edges. Wear gloves to
prevent cuts or abrasions when removing from carton, handling, installing and maintaining this product.
Lithonia Lighting assumes no responsibility for claims arising out of improper or careless installation or
handling of this product.
IMPORIMPOR
IMPORIMPOR
IMPOR
TT
TT
T
ANT SAFETY INSTRUCTIONSANT SAFETY INSTRUCTIONS
ANT SAFETY INSTRUCTIONSANT SAFETY INSTRUCTIONS
ANT SAFETY INSTRUCTIONS
RISK OF FIRE - Observe lamp
manufacturer’s warnings, recommenda-
tions and restrictions on lamp operation
and maintenance.
WARNINGWARNING
WARNINGWARNING
WARNING
Do not install a damaged fixture.
• This fixture must be wired in accordance
with the National Electrical Code and
applicable local codes and ordinances.
Proper grounding is required to ensure
personal safety. Be certain green lead
from the fixture is connected to supply
ground.
Use code compliant connectors for all
electrical connections.
ALL work should be done by a qualified
electrician.
WARNING: NEVER connect or disconnect
any component while power supply is
engaged.
DELIVERY: Upon receipt of fixture and accesso-
ries (packed separately), thoroughly inspect for
any freight damage. All damage should be
reported to the delivery carrier. Do not install
damaged fixtures. Compare the catalog de-
scription listed on the packing slip with the fix-
ture label on the inside of the housing to be sure
you have received the correct merchandise.
IMPORTANT SAFETY
INSTRUCTIONS
WARNINGWARNING
WARNINGWARNING
WARNING
Mini-Flood
Prior to Installation
Read carefully before installing light fixtures. If you do not understand these instructions,
please contact your local Lithonia distributor before installing.
INSTALLATION
LOCATION: The adjustable 1/2”NPS straight pipe thread knuckle can be easily mounted to a variety of
mounting configurations. This fixture should not be mounted within 6” of any flammable materials. Fixture
should be permanently mounted.
JUNCTION BOX MOUNTING
1. Thread aiming arm through the cover plate (not included) and tighten the locknut provided.
2. Make supply connections (described below), attach the cover plate to the junction box. Fixture must be
oriented so that the bulb is horizontal.
3. Loosen the side bolt connected to the arm knuckle to aim the fixture up or down. Re-tighten bolt to secure
the fixture in the desired position.
CONDUIT MOUNTING
1. Secure appropriate conduit fitting (not included) to floodlight knuckle.
2. Make supply connections (described below) and tighten fitting to conduit. Do NOT tighten fitting by
rotating entire fixture in the desired position.
3. Loosen the side bolt connected to the arm knuckle to aim the fixture up or down. Re-tighten bolt to secure
the fixture in the desired position. Fixture must be oriented so that the bulb is horizontal.
WIRING
Caution: Check that voltage is compatible with fixture ballast (120V). Use approved connectors for all
electrical connections.
1. Connect the black fixture lead to the black supply lead.
2. Connect the white fixture lead to the white supply lead.
3. Connect the green fixture lead to the green supply lead.
BULB INSTALLATION AND RE-LAMPING
1. When re-lamping, turn power off and allow the fixture to cool adequately.
2. Install the correct lamp (provided). Prior to installing the lamp in the fixture, check to be sure the lamp is of
proper type and wattage. Screw the lamp securely into the socket, back the lamp out one to two turns,
then screws the lamp back in, making sure it is secure. This properly seats the lamp in the socket.
3. Close the door frame and latch shut securely. Be sure that the gasket is firmly seated in the proper
channel prior to closing fixture to maintain weather-tight seal.
4. Re-connect the power.

Summary of content (1 pages)