Instructions / Assembly

FIXTURES WITH OPTIONAL BATTERY BACKUP ("EM14" OPTION)
JCBL fixtures supplied with the optional battery backup provide 90 minutes of reduced illumination after a power outage. The illumination under battery power is
approximately 1400 lumens with a full battery, then lumens decline as the battery power drains.
Fixtures are supplied with 2 sets of input wires. The battery controller input wires must be wired to a non-switched power source. The standard fixture input wires
can be connected to a switched or non-switched power source.
After fixture has been wired and power restored, the battery test switch should be illuminated. This means that the battery controller is receiving power and charging
the battery. Push the test button to confirm the fixture switches to battery mode. A single LED will light up, delivering approximately 1400 lumens.
After initial test, let the fixture charge for at least 48 hours, preferably longer, then longer tests can be performed.
Follow all local and National codes for testing and record keeping requirements.