Accupro Ballast Specification Sheet

CONTRACTOR SELECT / DOWNLIGHTING ACCUPRO
Catalog
Number
Notes
Type
Contractor Seelct Electronic Ballast Option
ACCUPRO
®
MVOLT
Instant Start
FEATURES & SPECIFICATIONS
NEMA Premium®, CEE qualied.
Normal ballast factor: 0.88.
Instant start.
Parallel circuit type.
Starting temperature is 0°F for 32W lamps; 60°F for energy-saving T8 lamps.
Input voltage: 120-277; 50Hz or 60Hz.
UL Listed Class P; CSA Certied.
ELECTRICAL SYSTEM
Ballast shall be instant start.
Ballast shall contain auto-restart circuitry to restart lamps without a reset of power.
Ballast shall operate input voltages 120-277, with variations of +/- 10% at 50Hz or 60Hz.
Ballast shall be a high-frequency electronic type, and operate lamps at a frequency above 42kHz to minimize
interference with infrared devices, eliminate visible icker and avoid Article Surveillance Systems.
Ballast shall have power factor greater than 0.98 for primary lamp.
Ballast shall have minimum ballast factor of 0.87 for primary lamp.
Lamp current crest factor shall be 1.7 or less, in accordance with lamp manufacturer recommendations.
Ballast shall have a less than 10% Total Harmonic Distortion (THD).
Ballast shall have a class A sound rating.
Ballast shall have a minimum starting temperature of 0°F for 32W T8 lamps, and 60°F for energy-saving
T8 lamps.
Ballast shall tolerate sustained open circuit and short circuit output conditions without damage.
Ballast shall not contain any PCBs.
Ballast shall comply with ANSI C62.41 Category A for Transient protection.
Ballast shall comply with ANSI C82.11.
Ballast shall comply with FCC part 18 non-consumer equipment for EMI/RFI (conducted and radiated).
Ballast shall be labeled "NEMA Premium".
Ballast shall be qualied with CEE.
Ballast shall be manufactured in facility certied to ISO 9001 standards.
Manufacturer shall have a ve-year history of producing electronic ballasts for the North American market.
LISTINGS
Ballasts shall be Underwriters Laboratory listed, Class P, Type 1 Outdoor, and CSA certied.
WARRANTY
Ballast shall carry a two-year warranty from the date of installation.
Specications subject to change without notice.
PERFORMANCE MATRIX
STANDARD 4' 32 WATT LAMP OPERATION
1
Input Input Input
Model Min. Power Ballast Wattage Current Current
Number
2
# Lamps BEF@277 factor factor 120/277 (A) 120V (A) 277V THD
A* 132-IP-UNV 1 Lamp >3.11 >0.98 0.87 30/28 0.25 0.11 <10%
A* 232-IP-UNV 2 Lamp >1.58 >0.98 0.88 56/55 0.50 0.20 <10%
A* 332-IP-UNV 3 Lamp >1.05 >0.98 0.88 85/83 0.73 0.31 <10%
A* 432-IP-UNV 4 Lamp >0.80 >0.98 0.88 112/109 0.94 0.42 <10%
ENERGY SAVING 4' 28 WATT LAMP OPERATION
Input Input Input
Model Min. Power Ballast Wattage Current Current
Number
2
# Lamps BEF@277 factor factor 120/277 (A) 120V (A) 277V THD
A* 132-IP-UNV 1 Lamp >3.52 >0.98 0.87 26/25 0.25 0.11 <10%
A* 232-IP-UNV 2 Lamp >1.76 >0.98 0.88 50/50 0.49 0.21 <10%
A* 332-IP-UNV 3 Lamp >1.16 >0.98 0.88 75/75 0.66 0.29 <10%
A* 432-IP-UNV 4 Lamp >0.88 >0.98 0.88 97/97 0.86 0.37 <10%
ENERGY SAVING 4' 25 WATT LAMP OPERATION
Input Input Input
Model Min. Power Ballast Wattage Current Current
Number
2
# Lamps BEF@277 factor factor 120/277 (A) 120V (A) 277V THD
A* 132-IP-UNV 1 Lamp >3.95 >0.98 0.87 23/23 0.20 0.09 <10%
A* 232-IP-UNV 2 Lamp >1.98 >0.98 0.88 44/44 0.41 0.18 <10%
A* 332-IP-UNV 3 Lamp >1.32 >0.98 0.88 69/66 0.60 0.26 <10%
A* 432-IP-UNV 4 Lamp >0.99 >0.98 0.88 90/88 0.82 0.35 <10%
(1) Also operates 17W 2' lamps
(2) Asterick (*) represents series number or letter