Installation Sheet
Page
1
INSTALLATION INSTRUCTIONS SUPPLEMENT
LQM OPTIONS FI AND X2
LQM STANDARD EXIT SIGN WITH FIRE ALARM INTERFACE
OR SECONDARY POWER SOURCE
IMPORTANT SAFEGUARDS
1.READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
2. Before wiring to power supply, turn off electricity at fuse or
circuit breaker.
3. Disconnect A.C. power before servicing.
4. All servicing should be performed by qualified personnel.
5. Consult your local building code for approved wiring and
installation.
6. Do not use outdoors.
7. Do not mount near gas or electric heater.
8. Fixture must be grounded to avoid potential electric shock.
9. Equipment should be mounted in location and at heights where
it will not readily be subjected to tampering by unauthorized
personnel.
10. The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
11. Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS
WIRING DIAGRAM
LQM STANDARD MODEL SHOWN
OPTIONS HIGHLIGHTED FOR LQM FI AND X2 INTERFACES
FOR LQM MODELS WITH FI INTERFACE ONLY:
NOTE: This exit fixture is provided with a FIRE ALARM (FLASHER)
INTERFACE to be cycled on and off and is intended for installation in
locations where permitted by local codes.
FLASH RATE 66 CPM
DUTY CYCLE 50/50
NOTE: TO BE USED WITH UNSWITCHED CIRCUIT ONLY.
Connect AC input leads as follows:
120V AC-BLACK PCB CONNECTOR LEAD
277V AC-ORANGE PCB CONNECTOR LEAD
NEUTRAL-WHITE PCB CONNECTOR LEAD
NOTE: Allow battery to charge 24 hours before initial testing, and 168
hours to fully charge battery.
CAUTION: For safety and proper operation, read and follow instructions carefully before installation.
FOR LQM MODELS WITH X2 OPTION ONLY:
CAUTION: This unit has more than power supply connection point. To
reduce risk of electrical shock, disconnect both the branch circuit
breaker or fuses and the emergency power supplies before servicing.
See manual for installation, operating, and maintenance instructions.
FI OPTION
(IF INSTALLED)
PC BOARD
120 V
NEUTRAL
277 V
BLACK
ORANGE
WHITE
COMMON
24 VDC 10mA (MAX)
CONTINUOUS
RED/WHITE
BLUE
(FROM FIRE
ALARM PANEL)
(TO AC POWER)
120 V
NEUTRAL
277 V
BLACK
ORANGE
WHITE
(TO AC POWER)
X2 OPTION