Specification
LQM
EMERGENCY: One Lithonia Way Conyers, GA 30012 Phone: 800.334.8694 Fax: 770.981.8141 www.lithonia.com ©1993-2017 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/16/17
LQM LED, Quantum
®
MOUNTING
All dimensions are inches (centimeters) unless otherwise specified.
Shipping weight: 2.6 lbs. (1.2 kgs.)
SPECIFICATIONS
5-5/8
(14.7)
7-5/8
(19.3)
7-5/8
(19.3)
3-7/8
(9.6)
8-3/8
(21.3)
11-3/4
(29.8)
11-3/4
(29.8)
5-7/8
(14.9)
4-1/2
(11.4)
2
(5.1)
Top Mounting
End Mounting
Back Mounting
ELECTRICAL
Primary Circuit
Type
1
Typical
LED life
2
Supply
voltage
Input
watts
Max.
amps
Red LED AC Only 10 years
120 .62 .05
277 .69 .06
Green LED AC Only 10 years
120 .62 .05
277 .74 .06
Red LED Emergency 10 years
120 .71 .05
277 .92 .06
Green LED Emergency 10 years
120 .66 .05
277 .70 .06
BATTERY
Nickel Cadmium
Voltage
Shelf
life
3
Typical
life
3
Maintenance
4
Optimum
temperature
5
1.2 3 years 7-9 years none 50°F - 104°F
(10°C - 40°C)
Notes
1 LED lamps operate in normal (AC input) and emergency (DC input) modes.
2
Based on continuous operation. The typical life of the exit LED lamp is 10 years.
3
At 77°F (25°C).
4 All life safety equipment, including emergency lighting for path of egress must be maintained, serviced and tested
in accordance with all National Fire Protection Association (NFPA) and local codes. Failure to perform the required
maintenance, service, or testing could jeopardize the safety of occupants and will void all warranties.
5 Optimum ambient temperature range where unit will provide capacity for 90 minutes. Higher and lower tempera-
tures affect life and capacity.