Installation Sheet

Page
2
INSTALLATION INSTRUCTIONS SUPPLEMENT
LQM EL N OPTIONS F, FA, AND FI
LQM EMERGENCY EXIT SIGN WITH FLASHING, FLASHING/AUDIBLE,
OR FIRE ALARM INTERFACE
CAUTION: For safety and proper operation, read and follow instructions carefully before installation.
FOR LQM EL N MODELS WITH F AND/OR FA OPTIONS ONLY:
NOTE: This exit fixture is provided with a FLASHER AND/OR
AUDIBLE feature and is intended for installation in locations where
permitted by local codes.
FLASH RATE 66 CPM
DUTY CYCLE 50/50
IMPORTANT SAFEGUARDS
1.READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
2. Before wiring to power supply, turn off electricity at fuse or
circuit breaker.
3. Disconnect A.C. power before servicing.
4. All servicing should be performed by qualified personnel.
5. Consult your local building code for approved wiring and
installation.
6. Do not use outdoors.
7. Do not mount near gas or electric heater.
8. Fixture must be grounded to avoid potential electric shock.
9. Equipment should be mounted in location and at heights where
it will not readily be subjected to tampering by unauthorized
personnel.
10. The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
11. Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS
FOR LQM EL N MODELS WITH FI INTERFACE ONLY:
NOTE: This exit fixture is provided with a FIRE ALARM (FLASHER)
INTERFACE to be cycled on and off and is intended for installation in
locations where permitted by local codes.
FLASH RATE 66 CPM
DUTY CYCLE 50/50
NOTE: TO BE USED WITH UNSWITCHED CIRCUIT ONLY.
Connect AC input leads as follows:
120V AC-BLACK PCB CONNECTOR LEAD
277V AC-ORANGE PCB CONNECTOR LEAD
NEUTRAL-WHITE PCB CONNECTOR LEAD
NOTE: Allow battery to charge 24 hours before initial testing, and 168
hours to fully charge battery.
WIRING DIAGRAM
LQM EMERGENCY MODEL SHOWN
OPTION HIGHLIGHTED FOR LQM EL N FI INTERFACE
PART NO. EMCSA00615
REV. A
FI OPTION
(IF INSTALLED)
PC BOARD
120 V
NEUTRAL
277 V
BLACK
ORANGE
WHITE
BATTERY
COMMON
24VDC 10 mA (MAX)
CONTINUOUS
RED/WHITE
BLUE
(FROM FIRE
ALARM PANEL)
(TO AC POWER)
EMERGENCY LIGHTING SYSTEMS