Specification
SPECIFICATIONS
LAMP COMPATIBILITY
PS600QD MVOLT Emergency Ballast
KEY OPTIONS
Self Diagnostics Module
RECOMMENDED SPACING
One Footcandle Average Fixture-to-Fixture Spacing Guidelines PS600QD MVOLT
KEY FEATURES
Quick-Disconnect wiring system
MOUNTING
All dimensions are inches (millimeters).
PS600QD MVOLT
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 888-300-7017 PS-support@acuitybrands.com www.acuitybrands.com © 1997-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/09/18
BATTERY
Sealed Nickel-Cadmium
Voltage
Typical Shelf
life
1
Typical life
1
Maintenance
2
Temperature
Range
3
4.8V 3 years 7-9 years none 32–100° F
Application 2GT8332 2SP8332 2PM3N332 2AV332 2PMO332
2x4
Open Office 32 35 34
26 35
Corrdior 40 43 53 34 40
2x2
Open Office 32 33 29 29 28
Corrdior 39 40 35 29 28
Lamp Type
Wattage
PS600QD MVOLT
Lumens 600-700
U-Lamp T8
32
1
24"-48" T8 17-32 1.2
48"-60" T8 32-40 1.2
Long Compact (4-Pin) 18-40 1
ELECTRICAL
Maximum AC input
Volts Amps Watts
120 .29 3.0
277 .29 3.0
1 FC average
0.1 FC min.
45'
9'
6'
CORRIDOR SPACING
Meets Life Safety Code standard minimum
illuminance of 0.1FC and average illuminance
of 1.0 FC. Assumes 3 T8 lamps in each fixture,
6-foot wide path of egress, ceiling height 9'
and reflectances of 80/50/20.
Fluorescent Battery Pack: PS600QD MVOLT
Fluorescent Fixture: Lensed Troffer
Lamp Type: F32T8
Cross section end view:
Length: 9.4 inches
Shipping weight: 1.5 lbs (0.68 kg).
SELF-DIAGNOSTICS
MODULE
New reduced-profile design fits in
the tightest of applications
Power SentryTypical
2-3/8” 2-3/16”
1-1/2"
1-3/16”
Notes
1 At 77° F.
2 All life safety equipment, including emergency lighting for path of egress must be maintained, serviced and
tested in accordance with all National Fire Protection Association (NFPA) and local codes. Failure to perform the
required maintainence, service or testing could jeopardize the safety of occupants and will void all warranties.
3 Ambient temperature range where unit will provide capacity for 90 minutes. Higher and lower temperatures
affect life and capacity. Consult factory for detailed information. Damp location models are UL listed 0-50
(32-122F).
Notes
* Based on the lumen output of the lamp; provides full light output.
1 One-lamp emergency operation for 1, 2, 3 or 4-lamp ballasts.
2 Two-Lamp emergency operation for 2, 2 or 4-lamp ballasts.
3 One-lamp, 2 hour emergency operation for 2, 3 or 4-lamp ballasts.