Installation Guide

1 of 3
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com © 2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 10/22/2020
INSTRUCTION
SHEET
SPECIFICATIONS
PHYSICAL SPECS
SIZE: 2.74”H x 1.68”W x 1.63”D
(6.96 cm x 4.27 cm x 4.14 cm)
(not including ground strap)
WEIGHT: 5 oz
MOUNTING: Single Gang Switch Box
MOUNTING HEIGHT: 30-48 in (76.2-121.9 cm)
ELECTRICAL SPECS
MAXIMUM LOAD (Relay)
800 W @ 120 VAC / 1200 W @ 277 VAC / 1500 W @ 347 VAC
MINIMUM LOAD: None
MOTOR LOAD: 1/4 HP
MAX SINK CURRENT: 50 mA
010V DIM MIN OUTPUT: <0.3 V
FREQUENCY: 50/60 Hz (timers are 1.2x for 50 Hz)
ENVIRONMENTAL SPECS
OPERATING TEMP: 14° to 122° F (-10° to 50° C)
RELATIVE HUMIDITY: 20 to 75% non-condensing
ROHS COMPLIANT
WSX D
Dimming Occupancy Wall
Switch
CONVERSION FROM GROUND ONLY NO NEUTRAL TO NEUTRAL WIRING
This product is pre-configured for wiring without a neutral with a solid ground; however, if connection to
neutral is required by code, the unit easily converts in seconds.
TROUBLESHOOTING
Unit does not appear to power up:
• Confirm device is properly connected to neutral or ground, per the wiring diagram above.
• Confirm all wiring connections and that 120/277VAC is present.
For further troubleshooting guidance, please contact the Controls Technical Support Team
1(800)-535-2465
Step 1:
Remove Yellow
Label
Step 2:
Loosen Screws and
Remove Metal Link
Step 3:
Connect Neutral to
Silver Screw & Ground
to Green Screw
WIRING TO GROUND NO NEUTRAL WIRING TO NEUTRAL
36 30 20 10 0 ft 10 20 30 36
12 9 6 3 0 m 3 6 9 12
Small
motion
detection
Small
motion
detection
to ~20 ft
6
3
0 m
20
10
0 ft
Small motion ~40 ft coverage
TOP VIEW
1.2 m
4 ft
Small motion
detection to ~20 ft
Large motion detection to >36 ft
SIDE VIEW
0 18 27 369
ft
0 6 9 123
m
TOP VIEW
36 30 20 10 0 ft
10 20
30 36
12 9 6 3 0 m
3 6 9 12
Small
motion
detection
Small
motion
detection
to ~20 ft
6
3
0 m
20
10
0 ft
Small motion ~40 ft coverage
TOP VIEW
1.2 m
4 ft
Small motion
detection to ~20 ft
Large motion detection to >36 ft
SIDE VIEW
0 18 27 369
ft
0 6 9 123
m
GND
H
LOAD
BLK
BLK
REMOVE METAL LINK
IF CONNECTING TO
NEUTRAL
VIO (+)
PNK (-)
DIMMING
H
H
LOAD
BLK
BLK
N
GND
VIO (+)
PNK (-)
DIMMING
H
120/277 VAC WIRING
BLACK* - Line Input
BLACK* - Load Output
VIOLET -Low Voltage Dim Output (0-10 VDC)
PINK -Low Voltage Common
*BLACK wires
can be reversed
}
WIRE COLOR KEY
347 VAC WIRING (-347 Option)
Red wires replace Black wires.
1.) Do not wire device hot.
2.) Per NEC requirements, the 0-10V violet and pink wires must be installed as Class One.
3.) 0-10V Dimming Common from luminaire may be pink or as otherwise indicated per section 410.69 of the
2020 NEC.
4.) The 0-10V control wires must not exceed 250 ft (76 m) in length and must be sized at no less than 20 AWG.
5.) If no neutral is present, unit requires a solid ground connection in order to power up.
COVERAGE PATTERN
Small motion (e.g. hand movements) detection up to 20 ft (6.10 m), ~625 ft
2
Large motion (e.g. walking) detection greater than 36 ft (10.97 m), ~2025 ft
2
Wall-to-wall PIR coverage
Units with -PDT (Passive Dual Technology) option (also called Microphonics
TM
) provide overlapping detection
of human activity over the complete PIR coverage area. Advanced filtering is utilized to prevent non-occupant
noises from keeping the lights on.