Install Instructions
Table Of Contents
- MODELS 201A
- 201A-9
- N/A
- RED
- RED
- GREEN
- GREEN
- Functional Characteristics
- Low Voltage
- Trip
- 90% of setting
- Reset
- 93% of setting
- High Voltage (201A-9 only)
- Trip
- 110% of setting
- Reset
- 107% of setting
- Voltage Unbalance
- Trip
- 6%
- Reset
- 4.5%
- Trip Delay
- High/Low Voltage and Unbalance
- 4 seconds
- Single-Phasing
- 2 seconds
- Restart Delay
- 2 seconds
- Input Characteristics
- Line Supply Voltage
- 190 to 480 VAC
- Frequency
- 50/60Hz
- Output Characteristics
- Output Contact Rating
- Pilot Duty
- 480VA @ 240VAC
- General Purpose
- 10A @ 240VAC
- General Characteristics
- Environmental
- Ambient Operating Temperature
- Relative Humidity
- 10-95%, non-condensing per IEC 68-2-3
- Maximum Input Power
- 5 W
- Standards Passed
- Electrostatic Discharge (ESD)
- IEC 61000-4-2, Level 3, 6kV contact, 8kV air
- Radio Frequency Immunity, Radiated
- 150 MHz, 10V/m
- Fast Transient Burst
- IEC 61000-4-4, Level 4, 4kV input power and controls
- Surge Immunity
- IEC
- IEC 61000-4-5, Level 4, 4kV line-to-line; Level 4, 4kV line-to-ground
- ANSI/IEEE
- C62.41 Surge and Ring Wave Compliance to a level of 6kV line-to-line
- Hi-Potential Test
- Meets UL508
- (2 x rated V +1000 V for 1 minute)
- Safety Marks
- UL listed (OT08 octal socket required)
- UL508 (File #E68520)
- CE
- IEC 60947-6-2
- Dimensions
- 1.750” H x 2.375” W x 4.125” D (with socket)
- Weight
- 9 oz.
- Enclosure
- Polycarbonate
- Mounting Method
- Plugs into OT08 Socket
- Wire Gauge
- 12-22 AWG Solid or Stranded
- Terminal Torque for P/N OT08 Socket
- 12 in. - lb
INSTALLATION
INSTRUCTIONS
Revision A1
Rapid City, SD, USA, 01/2010
MODELS 201A
201A-9
2880 North Plaza Drive, Rapid City, South Dakota 57702
(800) 843-8848 · (605) 348-5580 · fax (605) 348-5685
222 Disk Drive, Rapid City, SD 57701
(800) 843-8848 www.symcom.com