Install Instructions

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION!
FOLLOW NATIONAL, STATE, AND LOCAL CODES!
READ THESE INSTRUCTIONS ENTIRELY
BEFORE
INSTALLATION!
2880 North Plaza Drive, Rapid City, SD 57702 (800) 843-8848
INSTALLATION INSTRUCTIONS
FOR SYMCOM’S MOTORSAVER
MODEL 460
The Model 460 MotorSaver
is an auto ranging voltage monitor designed to
protect three-phase motors regardless of size. The MotorSaver
is used on
190-480 VAC, 50 to 60 Hz motors to protect from damage caused by single
phasing, low voltage, high voltage, phase reversal, and voltage unbalance.
CONNECTIONS
1. Mount the MotorSaver
in a convenient location in or near the motor
control panel. If the location is wet or dusty, the MotorSaver
should
be mounted in a NEMA 4 or 12 enclosure. The MotorSaver
can be
mounted to a back panel using two #6 or #8 x 5/8 screws or can be
snapped onto a DIN rail.
2. Connect L1, L2 and L3 on the MotorSaver’s terminal strip to the LINE SIDE
of the motor starter. (See Figure No. 1).
3. Connect the output relay to the circuitry to be controlled. For motor control,
connect the normally open contact in series with the magnetic coil of the
motor starter as shown in Figure No. 1. For alarm operation, connect the
normally closed contact in series with the control circuit as shown in Figure
No. 2.