Product Overview

www.littelfuse.com © 2018 Littelfuse POWR-GARD
®
Products
POWR-GARD
®
Fuse Datasheet
Rev: 062218
CLASS CC KLKR SERIES FUSES
2 of 2
Electrical Specifications
ORDERING
NUMBER
AMPERAGE
RATING
VOLTAGE
RATING
INTERRUPTING
RATING
WATTS LOSS AT 100%
RATED CURRENT (W)
WATTS LOSS AT 80%
RATED CURRENT (W)
TOTAL CLEARING I
2
T
(A
2
SEC) 200 kA
AGENCY
APPROVALS
RoHS
AC DC AC DC UL CSA
KLKR001.T 1 600 300 200 kA 20 kA 0.38 0.20 80
KLKR006.T 6 600 300 200 kA 20 kA 1.36 0.77 210
KLKR012.T 12 600 300 200 kA 20 kA 1.58 0.83 350
KLKR015.T 15 600 300 200 kA 20 kA 2.3 1.37 314
KLKR020.T 20 600 300 200 kA 20 kA 2.3 1.39 900
KLKR030.T 30 600 300 200 kA 20 kA 3.75 2.10 1720
Peak Let-Thru Curve
10000
100000
200000
100
1000
100
1000
10000
100000
1000000
30 A
25 A
20 A
15 A
12 A
PEAK LET-THRU IN AMPERES
AVAILABLE FAULT CURRENT
SYMMETRICAL R. M. S. AMPERES
05542001
Disclaimer Notice – Information furnished is believed to be accurate and reliable. However, users should independently evaluate the suitability of and test each product selected for their own applications. Littelfuse