18
VCL-45ULS SERIES
Designed for automatic collection and removal of condensate from air
conditioning, refrigeration and dehumidification equipment when gravity
drainage is not possible or practical. Also, suitable for high eciency oil and
gas-fired condensing furnace and condensing boiler equipment.
1 gallon collection tank
Vertical centrifugal pump design
1/5 hp, fan cooled, PSC motor
Stainless steel motor shaft
Automatic start and stop operation
Includes float (solid polymer) activated switch for automatic high-level water
detection (overflow detection switch)
Overflow detection switch: dual function NO and NC operation (set to NO from
factory for equipment shut down connection)
Overflow detection switch includes two 5" switch lead wires
3/8" O.D. copper tubing discharge
*Optional check valve adapter for 3/8" O.D. copper tubing/3/8" I.D. vinyl tubing
sold separately (Part Number 599064)
1-1/8" diameter inlet opening
Thermally protected motor
Maximum water temperature: 120 °F
6 ft, 3-conductor cable with grounded 3-prong plug
FEATURES
APPLICATIONS
Item No. Model HP
Input
Voltage
Hz
Amps
(FLA)
Watts
(kW)
Discharge Size
Performance GPH (LPH) @ Head
Shut-O
Ft.
PSI Cord Weight (lbs)
1 3 5 9 15'
553240 VCL-45ULS
1/5
115 60 3.5 185
3/8" (9.5 mm)
OD Copper
450 (1705.5) 445 (1686.6) 440 (1667.6) 415 (1572.9) 380 (1440.2) 45 (13.7 m) 19.5 6 (1.8 m) 13 (5.9 Kg)
553245 VCL-45ULS
1/5
230 50/60 1.0 250
3/8" (9.5 mm)
OD Copper
450 (1705.5) 445 (1686.6) 440 (1667.6) 415 (1572.9) 380 (1440.2) 45 (13.7 m) 19.5 6 (1.8 m) 14 (6.4 Kg)
SERIES SPECIFICATIONS