Installation Instructions

The drain hose must be arranged beneath the connecting pipe.
The drain hose must not be hunched or twisted.
While wrapping up the drain hose, do not pull it.
The drain hose through the room must be wrapped up by the
thermal insulation materials.
The connecting pipe and the drain hose must be wrapped up by felt
strip. Adiabatic pad should be used at where the pipe contacts
the wall.
NOTE:
1
2
3
ROUTE OF PIPE
If pipe comes out of the right side of the indoor unit, cut part
1 of the unit;
If pipe comes out of the lower-right side of the indoor unit, cut
part 2 of the unit;
If pipe comes out of the left side of the indoor unit, cut part 3
of the unit.
Installation of the drain hose
Wiring
2
Open the front grille;
Remove the screw from electrical box cover, pull the
electrical box cover away from the unit and set aside.
Remove the screw from fastener, pull the fastener
away from the unit and set aside.
Connect the cable.
Replace the fastener and electrical box cover.
Indoor unit terminal
Screw
Connecting cable
Diagram
3
4
Drain hose
gas pipe
Liquid pipe
felt
Adiabatic
underlay
NOTE:
NOTICE:
The holes at solid arrow position must be secured to avoid the shake of mounting plate.
When the expansion bolts are used, two holes ( 11× 20 or 11× 26 ) that the distance
between them is 450mm should be adopted.
Confirm the position of holes, and drill holes on the wall.
40mm
Pipe hole
plumb
fasten string at the central hole
at least 250mm
at least 180mm
at least 140mm
120mm
Center of hole(? 65mm)
Center of hole(? 65mm)
440mm
fasten string at the central hole
at least 80mm
230mm
440mm
at least 120mm
at least 120mm
¦
90mm
plumb
¦
90mm
Pipe hole
The appliance shall be installed in accordance with national wiring regulations.
The appliance must not be installed in the laundry.
The appliance must be installed 2.5m above the floor.
The appliance must be positioned so that the plug is accessible.
For some models whose cooling capacity are above 4600W (17000BTU/h),
an all-pole disconnection device which has at least 3mm separation distance in
all pole and a residual current device(RCD)with the rating of above 10mA shall
be incorporated in the fixed wiring according to the national rule.