Water Heater User Manual
1 Service 
Details Screen:
The Details Screen is accessed by pressing the DETAIL button 
on the Status Screen. This screen shows the status of the 
various safeties, inputs and outputs to each control module.  
Selection of the control module to be viewed is accomplished 
by pressing the SELECT button. The control module being 
displayed is shown in the module box.
Displayed items are as follows:
  •  HW Thermostat - Is ON when a Hot Water call has been 
   received from a tank thermostat. Is OFF when a Hot 
    Water call has not been received from a tank thermostat.
  •  Gas Pressure Switches - Is ON when the high and low gas 
    pressure switches are closed. If OFF when either the high 
    or low gas pressure switches are open.
  • Louver Proving Switch - Is ON when a remote proving 
    safety switch is closed. Is OFF when a remote proving 
    safety switch is open.
  •  Manual Reset High Limit - Is ON when the manual reset 
    high limit is closed. Is OFF when the manual reset high 
 limit is open.
  •  Air Pressure Switch - Is ON when the combustion air 
    blower is energized and the flap valve switch is closed.  
    Is OFF when the flap valve switch is open.
  • Flow Switch / Low Water Cutoff - Is ON when the low 
    water cutoff contacts are closed or if an optional flow 
    switch is used and it is closed as well. Is OFF when the 
    low water cutoff contacts are open or if an optional flow 
 switch is open.
14
  Service Manual
 •  Blocked Drain Switch - Is ON when the blocked drain 
    switch on the condensate trap is closed. Is OFF when the 
    blocked drain switch on the condensate trap is open.
  •  Auto Reset High Limit - An auto reset high limit is not used 
    in the standard configuration of the Armor X2 water 
    heater. If OFF is shown then a wiring problem exists.
  •  HW Pump - Is ON when a Hot Water Generation call has 
    been received from a tank thermostat or a tank sensor and 
    the hot water generation pump is energized. Is OFF when 
    the hot water generation pump is de-energized.
  •  Gas Valve - Is ON when the gas valve is energized. Is OFF 
    when the gas valve is de-energized. 
  •  Alarm - Is ON when a fault has been detected and the 
    alarm contacts are closed. Is OFF when the alarm 
 contacts are open.
  •  Blower Power - Is ON when the combustion air blower is 
    energized. Is OFF when the combustion air blower is de-
 energized.
  •  Run Time Contacts - Is ON when the burner is energized.  
    Is OFF when the burner is de-energized.
  •  0-10Vdc - Shows the voltage signal being delivered from a 
    remote Building Management System (BMS).