Cascade Parameters Screen:
Cascade Operation
When multiple water heaters are installed, they can be wired 
together in a cascade sequence. A maximum of eight (8) 
heaters can be controlled from a single control. In this 
application one heater would be designated as the Leader and 
all others would be designated as Members. The designated 
Leader water heater determines the total output needed from 
the group based on the set point and the tank sensor reading.  
Reference the Wiring of the Cascade section in the Armor 
X2 Installation and Operation Manual for more information 
regarding the cascade feature.
The Cascade Screen allows access to four (4) parameters.  
Those parameters are as follows:
 • Cascade Address - The heater designated as the Leader 
    should be programmed with address 0-1. All Member 
    heaters require addresses from 2-3 through 14-15. The 
    address must be different for each member. The 
    addresses can be in any order, regardless of the order in 
    which the water heaters are wired together. This 
    parameter can only be changed by the installer. The 
    default address is 0-1.
 • Cascade Off Differential - Sets how many degrees above 
    set point the temperature has to go before the lead water 
    heater will shut off. This parameter can only be changed 
    by the installer. The temperature range of this parameter 
    is 0° to 72°F. The default value is 10°F.
  • Cascade Off/On Differential - Sets how many degrees 
    below the turn off temperature (set point + Cascade Off 
    Differential) the temperature has to go before the lead 
    water heater will turn on. This parameter can only be 
    changed by the installer. The temperature range of this 
    parameter is 0° to 72°F. The default value is 20°F.
  • Maximum Outlet Temperature - Sets the set point that 
    individual heater will attempt to achieve in a cascade.  
    When a heater is commanded to fire by the Leader, it will 
    attempt to achieve this temperature at its outlet. The 
    Leader will control the modulation of the last heater to fire 
  in order to hold the temperature at the tank 
    sensor to the user set point. If any of the water heater 
  outlet temperatures reach the Maximum Outlet 
    Temperature setting, the water heater will then modulate 
    down on its own in order to keep its outlet temperature 
 within the Maximum Outlet Temperature setting.  
   Therefore, this parameter can be used to limit the 
    outlet temperatures of all the heaters in a cascade.
Reference page 17 for information regarding changing 
parameters.
Time - The time is displayed in the upper right-hand corner of 
the display. It is displayed in a 24 hour format. Reference the 
night setback parameters on page 21 for information regarding 
adjusting the date and time.
Back button - Pressing this button will back the screen up to the 
previous screen.