Water Heater User Manual
1 Service (continued)
23
0 - 10Vdc BMS Parameters Screen:
0-10Vdc Operation
When the Demand Configuration parameter (see page 18) 
is set to either Cascade BMS Thermostat Based, Cascade 
BMS Voltage Based, Cascade Modbus BMS Thermostat 
Based, or Cascade Modbus BMS Voltage Based; a 0 - 10Vdc 
signal can be supplied to the terminal strip connection or 
through Modbus communications to control a single unit or 
a multiple unit cascade.
The BMS Screen allows access to 12 parameters. Those 
parameters are:
  •  BMS Type - When the unit or cascade is controlled by the 
    0-10Vdc BMS input, the voltage signal can control either 
    the modulation rate or set point. This parameter can only 
    be changed by the installer. The default method of 
    control is modulation rate. 
  •  ModBus Time - When the tank temperature reading is 
    provided through the ModBus control, it should be 
    refreshed on a regular basis. This setting defines the 
    maximum time it must be refreshed. If the time expires, 
    the control will revert to its local reading. 
  • BMS Set Point at Minimum Voltage - Determines the set 
    point used by the unit or cascade when the BMS voltage 
    is at or below the setting of the BMS Voltage Minimum 
    Set Point parameter. This parameter is only active when 
    the BMS Type is set to Set Point. This parameter can only 
    be changed by the installer. The temperature range of this 
    parameter is 32° to 179°F. The default value is 70°F.
  •  BMS Set Point at Maximum Voltage - Determines the set 
    point used by the unit or cascade when the BMS voltage 
    is at or above the setting of the BMS Voltage Maximum 
    Set Point parameter. This parameter is only active when 
    the BMS Type is set to Set Point. This parameter can only 
    be changed by the installer. The temperature range of this 
    parameter is 70° to 190°F. The default value is 179°F.
  • BMS Voltage at Minimum Set Point - Determines the 
    voltage at which the external signal begins to increase the 
    set point. Below this voltage, the set point will be at the 
   setting of the BMS Set Point Minimum Voltage 
    parameter. This parameter is only active when the BMS 
    Type is set to Set Point. This parameter can only be 
    changed by the installer. The range of this parameter is 0 
    to 10V. The default value is 2V.
  • BMS Voltage at Maximum Set Point - Determines the 
    voltage at which the external signal forces the set point to 
    the setting of the BMS Set Point Maximum Voltage 
    parameter. This parameter is only active when the BMS 
    Type is set to Set Point. This parameter can only be changed 
    by the installer. The range of this parameter is 2V to 10V.  
    The default value is 10V.
  •  BMS Voltage at Start Call for Heat - When the Demand 
    Configuration parameter (see page 18) is set to Cascade 
    BMS Voltage Based, this parameter determines the BMS 
    input voltage at which the unit or cascade is enabled. The 
    unit or cascade will become enabled when the BMS input 
    voltage rises up to or above this value. This parameter can 
    only be changed by the installer. The range of this 
    parameter is 0 to 10V. The default value is 2V.
  • Drop in BMS Voltage to End Call for Heat - When the 
   Demand Configuration parameter (see page 18) is set to 
    Cascade BMS Voltage Based, this parameter determines the 
    BMS input voltage at which the unit or cascade is disabled.  
    The unit or cascade will become disabled when the BMS 
    input voltage drops down to or below the BMS voltage at 
    start call for heat minus this value. This parameter can only 
    be changed by the installer. The range of this parameter is 
    0 to 10V. The default value is 1V.
  Service Manual










